Interrupter Service Life; Accessories And Spare Parts - Siemens 3AH3 Operating Instructions Manual

Vacuum circuit-breaker
Hide thumbs Also See for 3AH3:
Table of Contents

Advertisement

Maintenance
Replacing spare parts
Accessory/spare part
Operating instructions
Hand crank
Lubricant
Vaseline (contact grease)
e. g. Atlantic white, Atlantic Mineralölwerk GmbH
56

Interrupter service life

If switching operations occur frequently under overload or short circuit, the service
life of the vacuum interrupters may be reached prematurely.
Replace the interrupters after reaching the maximum permitted operating cycle
number of 10 000 mechanical or electrical load setting changes (up to the rated cur-
rent).
When ordering vacuum interrupters, please always state the circuit-breaker type
and serial number (see "Rating plate" on page 35).

Accessories and spare parts

To ensure that the device operates reliably, spare parts must be replaced only by
trained and certified personnel.
CAUTION
Risk of injury!
The vacuum circuit-breaker should be taken out of the switch cabinet or switch-
gear for servicing.
Separate vacuum circuit-breakers from the control feed voltage or switch it off
and disconnect the low-voltage plug or clip connection.
Fig. 74
Accessories available for order
Always specify the vacuum circuit-breaker's type and serial no. (see "Rating plate"
on page 35) when ordering spare parts.
Order no.
9229 9860 100
3AX1530-2B
Comments
see "Special operating condi-
tions" on page 54
Pasty consistency, flame point
210 °C, low acid
9229 9860 176 0E
2013-08-22

Advertisement

Table of Contents
loading

This manual is also suitable for:

3ah333ah30

Table of Contents