Mounting
Undervoltage release (Y7)
available?
Fig. 64
Removing the cover
46
Removing the transport securing device from the undervoltage release
The vacuum circuit-breaker with an undervoltage release (Y7) 3AX1103 is supplied
with a transport securing device.
Remove the two top screws (60.2) of the mechanism box.
Remove the two bottom screws (60.2) of the mechanism box until the cover
(60.1) can be taken off.
Slightly tilt the cover (60.1) of the mechanism box and lift off.
Shift the locking screw of the striker from position A to B (see reference note in
mechanism box [60.] of the vacuum circuit-breaker).
Replace the cover (60.1) in the reverse order
and fasten the screws with a tightening torque of 10 Nm.
Fig. 65
Removing the transport securing device
A
B
9229 9860 176 0E