Siemens 3AH3 Operating Instructions Manual page 29

Vacuum circuit-breaker
Hide thumbs Also See for 3AH3:
Table of Contents

Advertisement

Fig. 38
2. Shunt release (54.2)
Fig. 39
Transformer-operated releases (54.3)
Siemens Parts
9229 9860 176 0E
2013-08-22
A further shunt release, transformer-operated release, undervoltage release or
instantaneous release can be installed as a 2nd release.
2nd shunt release (Y2) 3AX1101
Transformer-operated releases (Y4, Y5) 3AX1102, (Y6) 3AX1104
The second shunt release Y2 is installed whenever more
than one shunt release is needed.
In this version, the electrical "open" command is passed
by means of a magnet armature to the "OPEN" latch by
release of an energy storage mechanism, thus opening
the vacuum circuit-breaker. This opening solenoid is not
designed for continuous operation. Any necessary varis-
tors and rectifiers are integrated in the release.
Power consumption is approximately 60 W / VA
The transformer-operated releases Y4, Y5 or Y6 consist
of an energy storage mechanism, an unlatching fixture
and an electromagnetic system. If the tripping current is
exceeded (90 % of the transformer-operated release's
rated current), the energy storage mechanism is
unlatched, thus initiating opening of the vacuum circuit-
breaker.
For use of the transformer-operated release, matching
transformers are also needed for matching, in addition to
the main current transformers.
Power consumption for 0.5 A and 1 A ≤ 6 VA at ≤ 90 %
of the transformer-operated release's rated current and
with open armature.
Description
29

Advertisement

Table of Contents
loading

This manual is also suitable for:

3ah333ah30

Table of Contents