Gas Piping - Lochinvar LTN07575 Instruction Manual

Residential gas water heaters. not for use in manufactured (mobile) homes
Table of Contents

Advertisement

GAS PIPING

Contact your local gas service company to ensure
that adequate gas service is available and to review
applicable installation codes for your area.
Size the main gas line in accordance with
. The sizes shown are for straight lengths of pipe
Table 3
at 0.5 in. W.C. pressure drop, which is considered normal
for low pressure systems. Note: Fittings such as elbows,
tees and line regulators will add to the pipe pressure
drop. Also refer to the current editions of the
.
Gas Code (NFPA 54)
Make sure gas supplied is same type listed on model
rating plate. The inlet gas pressure must not exceed 14
inch water column (2.6 kPa) for natural and propane
(L.P.) gas. The minimum inlet gas pressure shown on
rating plate is that which will permit firing at rated input.
If the gas control valve is subjected to pressures
exceeding 1/2 pound per square inch (3.5 kPa), the
damage to the gas control valve could result in a fire or
explosion from leaking gas.
If the main gas line shut-off serving all gas appliances is
used, also turn "off" the gas at each appliance. Leave all
gas appliances shut "off" until the water heater installation
is complete.
A gas line of sufficient size must be run to the water
heater. Consult the current edition of
Gas Code ANSI Z223.1/NFPA 54
concerning pipe size.
The gas piping must include the following:
• A readily accessible manual shut off valve in the gas
supply line serving the water heater, and
• A sediment trap ahead of the gas control valve to help
prevent dirt and foreign materials from entering the
gas control valve.
and
Table 2
National Fuel
National Fuel
and your gas supplier
• A flexible gas connector or a ground joint union
between the shut off valve and control valve to permit
servicing of the unit.
Be sure to check all the gas piping for leaks before
lighting the water heater. Use a soapy water solution, not
a match or open flame. Rinse off soapy solution and wipe
dry.
The minimum inlet gas pressure shown on the rating
plate is that which will permit firing at the rated input.
GAS SUPPLY LINE SIZES (IN INCHES)* MAXIMUM CAPACITY
OF PIPE IN CUBIC FEET PER HOUR
TABLE 2. INPUT IN THOUSANDS (BTU/HR)
LENGTH
NOMINAL IRON PIPE SIZES (INCHES)
IN
1/2"
3/4"
1"
FEET
10
175
360
680
20
120
250
465
30
97
200
375
40
82
170
320
50
73
151
285
60
66
138
260
70
61
125
240
80
57
118
220
90
53
110
205
100
50
103
195
125
44
93
175
150
40
84
160
175
37
77
145
200
35
72
135
TABLE 3. INPUT IN KW
LENGTH
NOMINAL IRON PIPE SIZES (INCHES)
IN
METERS
1/2"
3/4"
1"
3
51
105
199
6
35
73
142
9
28
59
110
12
24
50
94
15
21
44
83
18
19
40
76
21
18
37
70
24
17
35
64
27
16
32
60
31
15
30
57
38
13
27
51
46
12
25
47
53
11
23
42
61
10
21
40
21
1 1/4"
1 1/2"
2"
2 1/2"
3"
1400
2100
3960
6300
11000
950
1460
2750
4360
7700
770
1180
2200
3520
6250
660
990
1900
3000
5300
580
900
1680
2650
4750
530
810
1520
2400
4300
490
750
1400
2250
3900
460
690
1300
2050
3700
430
650
1220
1950
3450
400
620
1150
1850
3250
360
550
1020
1650
2950
325
500
950
1500
2650
300
460
850
1370
2450
800
280
430
1280
2280
1 1/4"
1 1/2"
2"
2 1/2"
3"
410
615
1160
1845
3221
278
428
805
1277
2255
225
346
644
1031
1830
193
290
556
878
1552
170
264
492
776
1391
155
237
445
703
1259
143
220
410
659
1142
135
202
381
600
1083
126
190
357
571
1010
117
182
337
542
952
105
161
299
483
864
95
146
278
439
776
88
135
249
401
717
82
126
234
375
688
4"
23000
15800
12800
10900
9700
8800
8100
7500
7200
6700
6000
5500
5000
4600
4"
6735
4626
3748
3192
2840
2577
2372
2196
2108
1962
1757
1610
1464
1347