Clearances - Lochinvar LTN07575 Instruction Manual

Residential gas water heaters. not for use in manufactured (mobile) homes
Table of Contents

Advertisement

FIGURE 4. NORMAL FLAMES
If flames are seen to lift from the burner ports, gradually
close the air shutter until a stable flame is achieved. See
.
Figure 5
FIGURE 5. FLAME LIFTING
See
for the appearance of the half-closed and
Figure 6
full-closed air shutter. Normally, this flame lifting occurs
only at altitudes above 5,400 feet.
FIGURE 6. HALF-CLOSED AND CLOSED AIR SHUTTER
If the air shutter is closed too far, the flame will look hazy
and not have defined cones. See the example in
(page 10). In this case, the air shutter will need to be
7
opened. See
.
Figure 3
FIGURE 7. UNSTABLE FLAME

CLEARANCES

Minimum clearances between the water heater and
combustible construction are 0 inch at the sides and rear,
4" (102 mm) at the front, and 6" (153 mm) from the vent
pipe. Clearance from the top of the jacket is 12" (305
mm).
A gas water heater cannot operate properly without the
correct amount of air for combustion. Do not install in a
confined area such as a closet, unless you provide air
as described in
obstruct the flow of ventilation air. If you have any doubts
or questions at all, call your gas supplier. Failure to
provide the proper amount of combustion air can result in
a fire or explosion and cause death, serious bodily injury,
Figure
or property damage.
FIGURE 9. VENTILATION CLEARANCES
10
FIGURE 8. CLEARANCES
(page 16). Never
Air Requirements