FIGURE 12.
There must be a minimum of 6" (153 mm) clearance between single
wall vent pipe and any combustible material. Fill and seal any clearance
between single wall vent pipe and combustible surfaces with mortar
mix, cement, or other noncombustible substance. For other than single
wall, follow vent pipe manufacturer's clearance specifications. To insure
a tight fit of the vent pipe in a brick chimney, seal around the vent pipe
with mortar mix cement.
Failure to have required clearances between vent piping and
combustible material will result in a fire hazard.
Be sure vent pipe is properly connected to prevent escape of
dangerous flue gases which could cause deadly asphyxiation.
Chemical vapor corrosion of the flue and vent system may occur if
air for combustion contains certain chemical vapors. Spray can
propellants, cleaning solvents, refrigerator and air conditioner
refrigerants, swimming pool chemicals, calcium and sodium chloride,
waxes, bleach and process chemicals are typical compounds which
are potentially corrosive.

GAS PIPING

Make sure the gas supplied is the same type listed on the model rating
plate. The inlet gas pressure must not exceed 14 inch water column
(2.6 kPa) for natural and propane (L.P.) gas. The minimum inlet gas
pressure shown on the rating plate is that which will permit firing at
rated input.
If the gas control valve is subjected to pressures exceeding 1/2 pound
per square inch (3.5 kPa), the damage to the gas control valve could
result in a fire or explosion from leaking gas.
If the main gas line shut-off serving all gas appliances is used, also
turn "off" the gas at each appliance. Leave all gas appliances shut
"off" until the water heater installation is complete.
A gas line of sufficient size must be run to the water heater. Consult
the current edition of National Fuel Gas Code ANSI Z223.1/NFPA
54 and your gas supplier concerning pipe size.
There must be:
A readily accessible manual shut off valve in the gas supply line
serving the water heater, and
A drip leg (sediment trap) ahead of the gas control valve to help
prevent dirt and foreign materials from entering the gas control
valve.
A flexible gas connector or a ground joint union between the shut
off valve and control valve to permit servicing of the unit.
Be sure to check all the gas piping for leaks before lighting the water
heater. Use a soapy water solution, not a match or open flame.
Rinse off soapy solution and wipe dry.
The minimum inlet gas pressure shown on the rating plate is that
which will permit firing at the rated input.
Water heaters covered in this manual have been tested and approved
for installation at elevations up to 7,700 feet (2,347 m) above sea
level. For installation above 7,700 feet (2,347 m), the water heater's
Btu input should be reduced at the rate of 4 percent for each 1,000
feet (305 m) above sea level which requires replacement of the
burner orifice in accordance with the National Fuel Gas Code ANSI
Z223.1/NFPA 54. Contact your local gas supplier for further
information.
Failure to replace the standard orifice with the proper high altitude
orifice when installed at elevations above 7,700 feet (2,347 m) could
result in improper and inefficient operation of the appliance, producing
carbon monoxide gas in excess of the safe limits. This could result
in serious injury or death. Contact your local gas supplier for any
specific changes that may be required in your area.