Jumper Settings; Pushbuttons - K-TEK MT5000 Installation & Operation Manua

Guided wave radar level transmitter
Table of Contents

Advertisement

4.1.1. JUMPER SETTINGS

The jumper switches are located on the face of the electronics module and can be set up as follows (Figure 8).
ALARM (Left Jumper)
Placing the jumper to the lower position causes the output to go to 21.00 mA when there is a loss of signal or trans-
mitter malfunction.
Placing the jumper to the upper position causes the output to go to 3.62 mA when there is a loss of signal or trans-
mitter malfunction.
The alarm output works in conjunction with the ALARM DELAY setting available in the mA OUTPUT menu. The out-
put will go to alarm state only if there is a loss of signal that lasts at least the duration of the alarm delay. The alarm
delay default value is two seconds. For instance the output will hold the last measured value if there is a loss of sig-
nal lasting less than two seconds and will go into the alarm condition if the loss signal exceeds two seconds.
WRITE PROTECT (Right Jumper)
When the jumper is in the lower position the transmitter configuration cannot be changed manually or via HART®
communication. (Figure 8).
Placing the jumper in the upper position will allow the configuration parameters to be changed manually or via
HART® communication. (Figure 8).

4.1.2. PUSHBUTTONS

Three pushbuttons are located on the lower portion of the module faceplate (Figure 8). These buttons will be used
to navigate through the setup and configuration menu of the MT5000. Some operations will require the pushbuttons
to be used together or held for a period of time to affect a change.
Figure 8
Write Protect Jumper:
UP = OFF
DOWN = ON
Fault Jumper:
UP = Fail Low = 3.6 mA
DOWN =Fail High = 21.00 mA
LVL XX.XX in
Pushbuttons:
XX.XX mA
UP
DOWN
SELECT
MT5000-0200-1 Rev f (10-2010) DCN0528