Note The Power Requirements - Allen-Bradley ControlLogix 1756-IF6CIS Installation Instructions Manual

Sourcing current loop input module
Hide thumbs Also See for ControlLogix 1756-IF6CIS:
Table of Contents

Advertisement

Use an extended-depth cover (1756-TBE) for applications with heavy
gauge wiring or requiring additional routing space. When using an
IFM, consult the documentation that came with it to connect wiring.
Before you install your module, you should:
IMPORTANT
· install and ground a 1756 chassis and power supply.
· order and receive an RTB or IFM, and its
components, for your application.

Note the Power Requirements

This module receives power from the 1756 chasis power supply and
requires 2 sources of power from the backplane:
· 250mA at 5.1V dc
· 275mA at 24V dc
Add this current/power value (7.9W) to the requirements of all other
modules in the chassis to prevent overloading the power supply.
ControlLogix™ Sourcing Current Loop Input Module 5
Allen-Bradley
Publication
1756-IN579A-EN-P - March 2003

Advertisement

Table of Contents
loading

Table of Contents