Installation And Wiring; Before You Begin; Power Requirements; 1790D-4T0/T4T0 - Allen-Bradley CompactBlock LDX 1790D-T4T0 User Manual

I/o thermocouple modules
Table of Contents

Advertisement

Before You Begin

Power Requirements

1

Installation and Wiring

This chapter tells you how to:
• determine the power requirements for the modules
• avoid electrostatic damage
• install the module
• wire the module's terminal block

1790D-4T0/T4T0

The module receives system power from the DeviceNet network. An
auxiliary field supply provides power for the thermocouple/mV
channels.
Table 2.1 1790D-4T0/T4T0 Power Specifications
Power
Specification
DeviceNet
Supply voltage - 24V dc nominal
Voltage range - 11-28.8V dc
Power dissipation - 1.2W maximum @ 28.8V dc
Field
Supply voltage - 24V dc nominal
Voltage range - 21.6-26.4V dc (+10%)
Power dissipation - 1.5W maximum @ 26.4V dc

1790P-T4T0

The module requires external supplies for both system power and for
the thermocouple/mV channels.
Table 2.2 1790P-T4T0 Power Specifications
Power
Specification
PROFIBUS
Supply voltage - 24V dc nominal
Voltage range - 19.2-28.8V dc
Power dissipation - 2W maximum @ 28.8V dc
Field
Supply voltage - 24V dc nominal
Voltage range - 21.6-26.4V dc (+10%)
Power dissipation - 1.5W maximum @ 26.4V dc