C-6000 Model Identification - GAYLORD CG3 Series Technical Manual

Water-wash ventilators with model c-6000 command center
Table of Contents

Advertisement

OUTPUT
C-6000
MODULE
VERSION
MODEL #
This control will drive up to 10 damper motors (10 sections of ventilator with electric damper
motors). It requires a 100VA Transformer with a reset button.
Bottom Terminal = #19
Number of Fuses on Circuit Board = 4
# Damper Positioners = 1
6000-10 ICGL01-100
This module does not have GXT, CM, or #20 terminals on terminal strip TB1 . It does have a
GND (ground) terminal. It has 4 terminals on the TB2 terminal strip on the lower portion of the
board for the Damper Positioner.
It is necessary to add a Relay and a terminal GXT for GX2 ventilators with Electric Dampers and
normally closed thermostats, if required.
It is necessary to add a terminal CM for Cold Water Mist if required, it would be tied into #8.
This control will drive up to 10 damper motors (10 sections of ventilator with electric damper
motors). It requires a 100VA Transformer with a reset button.
Bottom Terminal = GXT
Number of Fuses on Circuit Board = 4
# Damper Positioners = 1
6000-10-A ICGL01-101
GXT, CM, and #20 terminals were added to and GND was removed from the TB1 terminal strip.
Relay #8 was added to accommodate GX2 (normally closed) thermostats.
It has 6 terminals on the TB2 terminal strip on the lower portion of the board. Terminals #5 and
#6 were added to the TB2 terminal strip to accommodate a 2nd Damper Positioner and the Fire
Test Switch.
** A Jumper is required from #6 from the TB2 terminal strip to #3 on the TB1 terminal strip.
This control will drive up to 10 damper motors (10 sections of ventilator with electric damper
motors). It requires a 100VA Transformer (Square D).
Bottom Terminal = GXT
Number of Fuses on Circuit Board = 6
# Damper Positioners = 0
6000-10-B ICGL02-102
Jumpers J1 and J2 were added to this board.
Fuses F5 and F6 were added to the circuit board.
Terminal #20 was removed from this board on the TB1 terminal strip. The terminals on TB2
were re-labeled as H1, H2, X1, X2, TS1, and TS2.
This control does NOT require a Damper Positioner.
This control will drive up to 14 damper motors (14 sections of ventilator with electric damper
motors). It requires a 250VA Transformer (Square D).
Bottom Terminal = GXT
Number of Fuses on Circuit Board = 6
# Damper Positioners = 0
6000-20-B ICGL02-102
Jumpers J1 and J2 were added to this board.
Fuses F5 and F6 were added to the circuit board.
Terminal #20 was removed from this board on the TB1 terminal strip. The terminals on TB2
were re-labeled as H1, H2, X1, X2, TS1, and TS2.
This control does NOT require a Damper Positioner.

C-6000 MODEL IDENTIFICATION

25
DESCRIPTION