EFFECTIVE DATE 04-2005 GAYLORD VENTILATOR TECHNICAL MANUAL FOR THE “CG3” SERIES WATER-WASH VENTILATORS WITH MODEL C-6000 COMMAND CENTER 10900 S.W. AVERY STREET • TUALATIN, OREGON 97062-1149 U.S.A. 1-800-547-9696 • 503-691-2010 • FAX: 503-692-6048 • email: info@gaylordusa.com...
Page 2
Gaylord Industries STREET ADDRESS: 10900 S.W. Avery Street, Tualatin, Oregon 97062-8549 U.S.A. PHONE: 503-691-2010 • 800-547-9696 • FAX: 503-692-6048 • email: gaylord@gaylordusa.com • www.gaylordusa.com COMMERCIAL KITCHEN EXHAUST SYSTEMS • FIRE PROTECTION • UTILITY DISTRIBUTION • ROOF TOP UNITS • POLLUTION CONTROL...
Page 4
CG3 VENTILATOR DESCRIPTIONS There are 5 different types of CG3 “Classic Gaylord”, water- Summary of CG3 Ventilators: wash ventilators. The differences involve the type and location The CG3 and CG3-FDL are very similar. Both have a damper of fire damper and whether the ventilator has a fire damper. The...
"CG3" SERIES VENTILATOR PRINCIPLE OF OPERATION GREASE EXTRACTION The Gaylord “CG3” Series Ventilator extracts up to 95% of the extraction baffle. There is a small sloped grease collecting grease, dust and lint particles from the airstream passing gutter on the back side of the damper which drains off liquefied through it, when operated and maintained in accordance with grease, preventing it from re-entraining into the airstream.
Page 7
"CG3" SERIES VENTILATOR PRINCIPLE OF OPERATION WASH CYCLE The wash cycle is activated each time the exhaust fan is shut off by pushing the “Start Wash” button on the Command COMMAND CENTER Center or as programmed on the clock. When activated the MODEL C-6000 exhaust and supply fans shut off, the damper control is SERIES...
Page 8
"CG3" SERIES VENTILATOR PRINCIPLE OF OPERATION INTERNAL FIRE MODE — For CG3 and CG3-FDT only! Automatic internal fire protection is accomplished by the 7. A red light on the Command Center illuminates. action of the thermostat(s), which are located at the point 8.
Page 9
The most common fire system is either a wet chemical type or the Gaylord Quencher water spray system. In the event of If the fire intensifies and the thermostat reaches 250°F, the fire a fire this system would normally be activated and discharged damper would then close and the exhaust fan would shut off.
Fire following occurs: retardant chemicals should never be applied to any portion of 1. The exhaust and supply fans shut off. The Gaylord Ventilator. If retardant is applied to the ventilator, it must be removed.
2. Check for proper velocity at air inlet slot. Refer to Pages 21 through 23 for method of checking velocity. Factory trained service agencies are certified by Gaylord Industries, Inc. to perform these inspections. For the name and 3. Test the "Internal Fire Mode" to check for proper damper phone number of your nearest agent visit our web site at closure.
DETERGENT PUMP OPERATION The Gaylord Ventilator detergent pump is an integral part of the PREVENTIVE MAINTENANCE wash-down system of The Gaylord Ventilator. The pump is As with any piece of fine equipment, a reasonable amount of located within the control cabinet unless otherwise specified.
DETERGENT FOR THE WASH SYSTEM FORMULA G-510 is the only cleaner recommended by Gay- lord Industries for use in the washdown system of The Gaylord Ventilator. FORMULA G-510 is a concentrated colloid cleaner LIMITED WARRANTY specially formulated to remove the daily accumulation of...
Programmed operations may include: catagories. An overview of the nine menu items are as follows: 1. Starting the exhaust fan once within a 24-hour period. 1. Service - Displays Gaylord's website address: 2. Stopping the exhaust fan and starting the wash cycle gaylordusa.com sequence once within a 24-hour period 2.
• Press [F3] to increase the Hour 1. Service • Press [F4] to increase the Minutes • Press [F6] [ENTER] to display Gaylord’s web site • Press [F1] to go to the Start time for the Wash on address: gaylordusa.com Sunday (Sun.Wash)
Page 16
MODEL C-6000 SERIES MENU FUNCTIONS t s i l i t ( " " e > > > t i x > s ’ > t i x l i t ( " " t > > > t i x >...
Page 17
MODEL C-6000 SERIES MENU FUNCTIONS c i t c i t > > > t i x > l i t ( " " e S “ ” e h t i " r f " A " f " ) c i >...
ENGINEERING DATA FIG. 10A TYPICAL ARRANGEMENT WITH VACUUM BREAKER/CHECK VALVE FOR BACKFLOW PREVENTION FIG. 10B TYPICAL ARRANGEMENT WITH BUILT-IN “RP” DEVICE FOR BACKFLOW PREVENTION...
ENGINEERING DATA Each Gaylord Ventilator is engineered to properly ventilate ELECTRICAL REQUIREMENTS the specific cooking operation. The exhaust air volume is en- Standard voltage 120 volt, 50/60 Hz. Provide 24 hour, 20 amp gineered as a specific volume per lineal ft. of ventilator and is service.
If there is still continuous discharge it potable water. The unit provided in the Gaylord control cabinet indicates that foreign material is preventing the first is manufactured by Watts Regulator Co.
MEASURING INLET SLOT VELOCITY Smoke capture and grease extraction efficiency are depen- Air velocity readings less than what is specified on the “Air dent upon the proper air velocity at the inlet slot of the ventilator. Velocity Chart” may allow smoke and grease to escape the confines of the ventilator and/or reduce grease extraction The “Air Velocity Chart”...
Page 22
The standard instrument used for measuring the inlet velocities 1. It is first necessary to determine if the ventilator includes on a Gaylord Ventilator is a Pacer, Model DA40 or DA4000 Custom Air baffles as shown in fig. 12B. If shop drawings are Digital Anemometer.
Page 23
°F LINEAL FT. OF HOOD AS AN EXHAUST HOOD WITHOUT EXHAUST DAMPER WHEN EQUIPPED 6. REFER TO GAYLORD VENTILATOR TECHNICAL MANUAL FOR INLET SLOT VELOCITY REQUIREMENTS AND METHOD OF CHECKING VELOCITY WITH FIRE DAMPER LOCKOUT PART NUMBER FDL. 7. ELECTRICAL RATING OF LIGHT FIXTURES: 120 VOLT, 60 HZ. OR 220 VOLT, 50 HZ.
(Refer to Figure 14) When the exhaust fan is B. Check the cold water mist hand valve in the control started, the solenoid valve in the cold water loop in the Gaylord cabinet to ensure that it is in the “Open” position.
C-6000 MODEL IDENTIFICATION OUTPUT C-6000 MODULE DESCRIPTION VERSION MODEL # This control will drive up to 10 damper motors (10 sections of ventilator with electric damper motors). It requires a 100VA Transformer with a reset button. Bottom Terminal = #19 Number of Fuses on Circuit Board = 4 # Damper Positioners = 1 6000-10 ICGL01-100...
TROUBLE-SHOOTING PLC STATUS LIGHT CHARTS The following is a list of how the status lights will appear on the PLC (Programmable Logic Controller) that is operating correctly. STANDARD (SINGLE OR SEQUENTIAL WASH) DESCRIPTION - PLC (Inputs) On while “Fire Test Switch” is pushed and held, or hood is in Internal Fire Mode. Off during "Cool Down Cycle"...
TROUBLE-SHOOTING C-6000, C-6000-A and C-6000-B Terminal Voltages (See page no. 25 to determine which model is present) TERMINAL DESCRIPTION FAN OFF FAN ON WASH ON INT. FIRE EXT. FIRE Main Power Connection : Hot 120 VAC 120 VAC 120 VAC 120 VAC 120 VAC Main Power Connection : Neutral...
This Control Cabinet Is Used When A Reduced Pressure Principle Device Backflow Preventer Is Not Required And A Vacuum Breaker Is Allowed For Backflow Prevention TYPICAL VACUUM BREAKER CHECK VALVE ARRANGEMENT MODEL "GPC-6000-VB" SERIES CONTROL CABINET GAYLORD DESCRIPTION PART NO. Ball Valve ..............(Specify Size) Solenoid Valve A.
MODEL GPC-6000 SERIES CONTROL CABINET This Control Cabinet Is Used When A Reduced Pressure Principle Device Backflow Preventer Is Required. MODEL "GPC-6000" SERIES CONTROL CABINET GAYLORD DESCRIPTION PART NO. Solenoid Valve (Specify Size) A. Replacement Coil (120 Volt) ........ 10156 (220 Volt) ........
MODEL GPC-6000-S SERIES CONTROL CABINET This Control Cabinet Is Used When Ventilators Are Washed In Sequence Groups. MODEL "GPC-6000-S" SERIES CONTROL CABINET GAYLORD DESCRIPTION PART NO. Solenoid Valve (Specify Size) A. Replacement Coil (120 Volt) ........ 10156 (220 Volt) ........
This illustration shows the cold water mist loop only. Parts for the hot water loop are shown on pages 33, 34 and 35. MODEL "GPC-6000-CM" SERIES CONTROL CABINET GAYLORD DESCRIPTION PART NO. 1/2" Ball Valve .............. 11258 1/2" Solenoid Valve NC ..........
MODEL C-6000 OR C-6000-A SERIES CONTROL GAYLORD NO. DESCRIPTION PART NO. MFG PART NO. Programmable Logic Controller (PLC) w/ Program 75634 24VDC Power Supply 18863 Fire Test Switch 16894 Damper Positioner 18876 Output Module 18779 PLC to Operator Interface Cable...
MODEL C-6000-B SERIES CONTROL C -6 0 0 0 -E S P -S C o m p o n e n t S c h e d u l e (1 -3 T r a n sfo r m e r s/ H i g h V o l ta g e P o w e r S u p p l y s) P C .
DAMPER CONTROL MOTOR AND CG3-FDL WIRING Used in CG3, CG3-FDL, and CG3-FDT only P C. G AYL O RD DES CRIP T IO N NO . P AR T N O . F or C-6000 or C-6000-A : 30204 Dam per Control M otor - A F 24-S R (24 V olt) ------------------------------------ F or C-6000-B : Dam per Control M otor - A F24-M FT P -10050 (24 V olt)
STANDARD VENTILATOR MODELS Model CG3-BDL Model CG3-BDL-CL Application - Wall mounted canopy Application - For single island style for all types of equipment. arrangements Model CG3-BDL-DS Model CG3-BDL-BB Application - For island style Application - For island style cooking arrangements where one side cooking arrangements over all of the cooking line is light duty equipment duties of equipment.
METRIC CONVERSION CHART DIMENSIONS (Feet and Inches) WATER FLOW/VOLUME TO CONVERT MULTIPLY BY TO CONVERT MULTIPLY BY in ......mm ....25.4 U.S. ounce ..... Liters ....02958 in ......cm ....2.54 U.S. gal ....Liters ....3.785 mm ......in ....0.03937 Liters ......
FIRE MODE TEST: 1. Kitchen make-up air supply is turned on______Yes______No CAUTION: Before any fire tests are performed, check with building superintendent to see if Gaylord control 2. Type of make-up air cabinet is tied into building alarm, monitoring system and/or Fire Department.
The Manufacturer’s obligation under this warranty and any warranties implied by law shall be limited to repairing or replacing at its option any part of said equipment when either Gaylord Industries, Inc. or the Licensed Gaylord Manufacturer’s examination shall disclose to its satisfaction to be thus...