C-6000, C-6000-A And C-6000-B Terminal Voltages - GAYLORD CG3 Series Technical Manual

Water-wash ventilators with model c-6000 command center
Table of Contents

Advertisement

TERMINAL
L1
Main Power Connection : Hot
L2
Main Power Connection : Neutral
1
Output to Supply Fan Motor Starter
2
Output to Detergent Pump
3
Thermostat Return
4
Fused Supply to PLC Outputs & Etc.
5
120 VAC Neutral Leg
8
Output to Exhaust Fan Motor Starter
CM
Output to Cold Water Mist Solenoid
9
Output to Wash Solenoid Valve #1
10
Output to Wash Solenoid Valve #2
11
Output to Wash Solenoid Valve #3
12
Output to Wash Solenoid Valve #4
13
Output to Wash Solenoid Valve #5
SF1
N.O. Dry Contacts for Supply Fan
SF2
Remote Control Center
EF1
N.O. Dry Contacts for Exhaust Fan
EF2
Remote Control Center
A1
N.O. Dry Contacts for Interface to
A2
Building Fire Alarm / Monitor System
Q1
N.C. Dry Contacts for Interface to
Q2
Fire System Fuel Shutoff Control
FS
Input from Remote Fire Switch
(1)
LD
Input from Detergent Flow Switch
(2)
LD
Input from Detergent Flow Switch
GX
Power for GX2 Damper Actuators
15
Output to Thermostat(s)
17
24 VAC Common
18
CG3 Damper Drive Signal [1-10]
18
CG3 Damper Drive Signal
19
Power for CG3 Damper Actuators
(3)
20
CG3 Damper Drive Signal [11-20]
Thermostat Return for GX2 Hoods
GXT
(1)
120 VAC - A jumper is installed between LD and #4 or Jumper J1 is present (No LD/Detergent Flow Switch Present)
(2)
120 VAC - LD (Detergent Flow Switch) is installed and Detergent Pump is running and Detergent is present
0 VAC
- LD (Detergent Flow Switch) is installed and Detergent Pump is running and Detergent is NOT present
(3)
#20 is only present on the C-6000-A control
#20 only has voltage when there are 2 Damper Positioners present (C-6000-20), otherwise voltage is 0 VAC
TROUBLE-SHOOTING

C-6000, C-6000-A and C-6000-B Terminal Voltages

(See page no. 25 to determine which model is present)
DESCRIPTION
FAN OFF FAN ON WASH ON INT. FIRE EXT. FIRE
120 VAC 120 VAC
120 VAC
0 VAC
120 VAC
0 VAC
0 VAC
120 VAC
0 VAC
0 VAC
120 VAC 120 VAC
120 VAC
High Voltage Common
0 VAC
120 VAC
0 VAC
120 VAC
0 VAC
0 VAC
120 VAC
0 VAC
0 VAC
120 VAC
0 VAC
0 VAC
120 VAC
0 VAC
0 VAC
120 VAC
0 VAC
0 VAC
120 VAC
Open
Closed
Open
Closed
Open
Open
Closed
Closed
0 VAC
0 VAC
NO Low Detergent Sensor (Jumper J1 is present)
120 VAC 120 VAC
120 VAC
Low Detergent Sensor (Jumper J1 is cut or NOT present)
0 VAC
0 VAC
0 VAC
24 VAC
24 VAC
24 VAC
24 VAC
Low Voltage Common
C-6000 or C-6000-A
14 VDC
6 VDC
14 VDC
C-6000-B
24 VAC
0 VAC
24 VAC
24 VAC
24 VAC
24 VAC
14 VDC
6 VDC
14 VDC
24 VAC
24 VAC
24 VAC
32
120 VAC
120 VAC
Common
0 VAC
0 VAC
0 VAC
0 VAC
0 VAC
0 VAC
24 VAC
0 VAC
120 VAC
120 VAC
0 VAC
0 VAC
120 VAC
0 VAC
0 VAC
120 VAC
120 VAC
120 VAC
120 VAC
120 VAC
120 VAC
120 VAC
120 VAC
120 VAC
120 VAC
120 VAC
Open
Open
Open
Open
Open
Closed
Open
Closed
Closed
Closed
Open
Open
0 VAC
0 VAC
120 VAC
120 VAC
120 VAC
0 VAC
0 VAC
0 VAC
0 VAC
0 VAC
24 VAC
24 VAC
24 VAC
6 VDC
6VDC
0 VAC
0 VAC
0 VAC
24 VAC
6 VDC
6VDC
24 VAC
24 VAC