Installation procedure

Personal injury . Sheds on epoxy encapsulation have
sharp edges . Wear protective gloves when handling the
unit . Failure to do so can result in cuts and abrasions .

Check-out procedure

1.
Check data plate . Make sure that ratings on the data
plate are correct for the planned installation.
2.
Visually inspect the switch . Visually inspect the
switch for any damage to bushing sheds, terminals,
tank, of trip handle.
3.
Install the switch . Follow locally approved installation
procedures. Mounting hardware is available for pole
mounting as an accessory.

High-voltage connections

1.
Ground the switch . Make the ground connection to
the ground connector located on the switch bracket of
the switch.
2.
Make line connections . Connect the primary leads
to the switch terminals. The universal clamp-type
terminals accommodate AWG No. 8 solid through 2/0
stranded conductor.
3.
Recommended torque levels for line and load terminal
hardware are 20–22 ft-lbs (27 .1–29.8 N-m) not to exceed
30 ft-lbs (40.7 N-m).
Hazardous voltage . Solidly ground all equipment . Failure
to comply can result in death, severe personal injury,
and equipment damage .
This equipment is not intended to protect human
life . Follow all locally approved procedures and safety
practices when installing or operating this equipment .
Failure to comply can result in death, severe personal
injury and equipment damage .
CAUTION
WARNING
WARNING
InstallatIon and operatIon InstructIons MN230007EN February 2017
Edison™ Single-Phase Vacuum Capacitor Switch

Control wiring

Connections to the actuating mechanism are made through
the standard five-pin (or optional six-pin) receptacle at the
bottom of the switch.
T258 .1
Mating plugs for the receptacle may be ordered separately.
Maximum cable and wire sizes accommodated by the plugs
are indicated in Table 2.
Table 2 . Control wiring specifications
Accessory Mating Plug
Number of Pins
5
6
Pin orientation diagrams for the accessory receptacles are
shown in Figure 1.
E
A
D
C
B
5-pin
Receptacle
Figure 1 . Receptacle pin orientation

Three-wire control

Remote control of the Edison capacitor switch is supplied
T223 .2
by a single-pole, double-throw switch (three-wire control)
supplied by the customer. Any manual switch, relay contact,
time switch, voltage-, current- or photo-electric-controlled
switch, or similar device can be used, provided the control
circuit is energized for a minimum of 80–100 ms for each
operation. Eaton requires a 10-second cool-down period
between open and close operations to ensure the
switch coil does not overheat or become damaged .
G102 .1
A connection diagram for a standard three-wire control is
shown in Figure 2.
Cable Range O.D.
Max. Wire Size AWG
11–14 mm (0.437–0.562 in.)
12
13–16 mm (0.500–0.625 in.)
16
KEY
F
E
D
C
6-pin
Receptacle
A
B
3