1MRK 500 127-UEN D
Fault indication
Internal Fail
Runtime App Error
Internal Fail
IEC 61850 Error
Internal Fail
DNP3 Error
Internal Fail
PSM1-Error
Internal Fail
BIM3-Error
Internal Fail
BOM4-Error
Internal Fail
IOM5-Error
Internal Fail
NUM30-Error
Internal Fail
SLM301-Error
9.2.2

Warnings

The warning message associated with the fault is found in the internal event list in the LHMI
menu Main menu/Diagnostics/Internal events. The message includes the date, time,
description and signal state for the fault. The current status of the internal fault signals can
also be checked via the LHMI in Main menu/Diagnostics/IED status/General.
When a fault appears, record the fault indication message and state it when ordering service.
Table 21:
Warning indication
Warning
IEC 61850 Error
Warning
GOOSE Error
Warning
DNP3 Error
9.2.3

Additional indications

The additional indication messages do not activate internal fault or warning.
The messages are listed in the LHMI menu under the event list. The signal status data is found
under the IED status and in the internal event list.
670 series
Operation manual
Warning indications
Additional information
IEC 61850 has not
succeeded in some actions
such as reading the
configuration file, startup
etc.
One or more access point is
not able to run GOOSE due
to GOOSE being
deactivated on the access
point, or the access point
being deactivated or failing.
Error in DNP3
communication.
Additional information
One or more of the application threads are not in an expected
state.
IEC 61850 has not succeeded in some actions such as reading
the configuration file or start-up.
An error in DNP3 communication has occurred.
A PSM card error has occurred. The instance number is shown
as part of the fault indication, such as 1 in this example.
A binary-in-module error has occurred. The instance number is
shown as part of the fault indication, such as 3 in this example.
A binary-out-module error has occurred. The instance number is
shown as part of the fault indication, such as 4 in this example.
A in/out-module error has occurred. The instance number is
shown as part of the fault indication, such as 5 in this example.
A NUM card error has occurred. The instance number is shown
as part of the fault indication, such as 30 in this example.
A SLM card error has occurred. The instance number is shown
as part of the fault indication, such as 301 in this example.
Section 9
Troubleshooting
GUID-7BAFA38E-5163-4E01-A7C3-6489B42233C7 v5
GUID-69561C77-50E8-45E2-B8AC-80116222B5B9 v3
81