ABB Relion 670 series Operation Manual page 85

Hide thumbs Also See for Relion 670 series:
Table of Contents

Advertisement

1MRK 500 127-UEN D
be blocked. This condition will be indicated with a sub-menu under Hints, where details about
this condition are shown. The Hint menu is a way to assist the user in troubleshooting.
The supported list of hints are as follows:
Table 19:
Headline
Incorrect setting of SyncLostMode
Sampled value substituted
Time diff: IED vs Sampled value
Frequency diff: IED vs Sampled value
Wrong cycle time for PMU report
PMU not connected to 3ph output
Invalid value set for PMU Parameters
Invalid phase angle reference
GOOSE is configured on a disabled port
Table continues on next page
670 series
Operation manual
The Hint menu is currently only available in English. All the entries are in English,
regardless of which language is selected.
Hint menu
Explanation
There are two explanations possible:
SyncLostMode is set to Block , no time source is
configured to achieve the required accuracy. Unless a
high accuracy time source is selected, the function
dependent on high time accuracy will be blocked.
SyncLostMode is set to BlockOnLostUTC , but there is
no UTC capable synch source (GPS, IRIG-B) used.
Unless a UTC capable time source is selected, the
function dependent on high time accuracy will be
blocked.
<Access Point><Hardware Module Identifier><svID>
Where the Hardware Module Identifier is the same as
given in PCM600, e.g. AP1: MU1_9201 svID:
<ABB_MU0101>
<Access Point><Hardware Module Identifier><svID>
Where the Hardware Module Identifier is the same as
given in PCM600, e.g. AP1: MU1_9201 svID:
<ABB_MU0101>
<Access Point><Hardware Module Identifier><svID>
Where the Hardware Module Identifier is the same as
given in PCM600, e.g. AP1: MU1_9201 svID:
<ABB_MU0101>
Wrong cycle time on SMAI or 3PHSUM block
connected to Phasor Report block. The SMAI or
3PHSUM block should have the same cycle time as
that of Phasor Report.
The PMU phasor report input(s) must be connected
to the 3ph output of SMAI or 3PHSU.
There are two explanations possible:
Check if the following parameters are set correctly on
PMUREPORT:
ReportRate or SvcClass or parameter
PRIMVAL:1.FrequencySel is not set as 50Hz / 60Hz.
Check if the following parameters are set correctly on
PMUREPORT:
ReportRate or SvcClass or RptTimetag
or parameter PRIMVAL:1.FrequencySel is not set as
50Hz / 60Hz.
PhaseAngleRef corresponds to an
The selected
analog channel that is not configured. Please
configure a valid reference channel.
At least one of the access points configured for
GOOSE is disabled. The port can be disabled either
through changing the access point operation to off
or by unchecking the GOOSE protocol from the
access point in the Ethernet configuration in PCM600
or LHMI.
Please enable GOOSE on access points: AP_FRONT,
AP_1
Section 9
Troubleshooting
79