272 Actual signals and parameters
All parameters
No.
Name/Value
8118 AUTOCHNG
INTERV
-0.1 = TEST
MODE
0.0 = NOT SEL
0.1...336.0 h
www.aotewell.com
Description
Controls operation of the Autochange function and sets the
interval between changes.
The Autochange time interval only applies to the time when
the speed regulated motor is running.
See parameter
8119 AUTOCHNG LEVEL
the Autochange function.
The drive always coasts to stop when Autochange is
performed. Autochange enabled requires parameter
INTERLOCKS
> 0.
WARNING! When enabled, the Autochange function
requires the interlocks
enabled. During Autochange the power output is interrupted
and the drive coasts to stop, preventing damage to the
contacts.
Relay logic
-0.1: Test mode. Forces the interval to value 36...48 s.
0.0: Disables the Autochange function.
0.1...336 h: The operating time interval (the time when the
start signal is on) between automatic motor changes.
sales@aotewell.com
for an overview of
(8120 INTERLOCKS
PFC with Autochange mode
Industry Automation
Def/FbEq
0.0 = NO
T SEL
8120
> 0)
1 = 0.1 h
+86-755-8660-6182