All parameters
No.
Name/Value
4023 PID SLEEP
LEVEL
0.0...500.0 Hz
4024 PID SLEEP
DELAY
0.0...3600.0 s
www.aotewell.com
Description
Defines the start limit for the sleep function. If the motor
speed is below a set level (4023) longer than the sleep
delay (4024), the drive shifts to the sleeping mode: The
motor is stopped and the control panel shows alarm
message
PID
SLEEP.
Parameter
4022 SLEEP SELECTION
INTERNAL.
Reference
Sleep boost step
(4031)
Selected process actual
value
Wake-up level
deviation (4025)
Output
frequency
t
= Sleep delay
sd
(4024)
t < t
sd
Sleep level
(4023)
Sleep start level
Defines the delay for the sleep start function. See parameter
4023 PID SLEEP
LEVEL. When the motor speed falls below
the sleep level, the counter starts. When the motor speed
exceeds the sleep level, the counter is reset.
Sleep start delay
sales@aotewell.com
Actual signals and parameters 243
must be set to
Sleep boost time (4030)
Wake-up delay
(4026)
Control
panel:
t
PID SLEEP
sd
Stop
Start
Industry Automation
Def/FbEq
0.0 Hz
t
t
t
1 = 0.1 Hz
60.0 s
1 = 0.1 s