Technical Data - nvent RAYCHEM HWAT-ECO Installation And Operation Manual

Hot water temperature maintenance system electronic controller
Table of Contents

Advertisement

1
General Information
1.3

Technical Data

Use
Maintain temperature
setpoint
Hot water piping
ambient temperature
Controller ambient
temperature
Switching capacity
Operating voltage
Internal power
consumption
Circuit protection
(not provided with
HWAT-ECO controller)
Power terminal block
Internal temperature
alarm
BMS control voltage
BMS cable maximum
length
Raychem-IM-H57340-HWATECOcontroller-EN-1805
Only for HWAT-Y2 and
HWAT-R2 heating cables
105˚F (40˚C) to 140˚F
(60˚C)
60˚F (15˚C) to 80˚F (25˚C)
40˚F (5˚C) to 105˚F (40˚C)
ambient
24 A 208/240 Vac max.
208/240 (±10%), 60 Hz
2.5 W
Max. 30 A with 30 mA
ground-fault protection
16–10 AWG (1.5–4 mm
Use copper conductors
only
150˚F (65˚C)
0–10 Vdc
328 ft (100 m)
2
)
nVent.com | 3