Description
Fig. 47
Ambient conditions
Insulating capacity
Fig. 48
Altitude correction factor K
36
Ambient conditions
Installation altitudes
The insulating capacity of insulation in air decreases with rising altitude due to the
lower air density. In conformity with IEC 62271-102, the rated lightning impulse
withstand voltage values given in Fig. 45 are valid up to an installation altitude of
1,000 m above sea level.
As from an altitude of 1,000 m, the insulation level must be corrected as shown in
Fig. 48:
a
3AH37/38vacuum circuit-breakers are suitable for use in
the following climate classes in accordance with
IEC 60721, Part 3-3:
•
Climatic ambient conditions:
•
Biological ambient conditions:
•
Mechanical ambient conditions:
•
Chemically active substances:
•
Mechanically active substances:
1) Peak value of the 24-hour means: +35 °C
2) Without ice formation and wind-driven precipitation
3) Without occurrence of salt fog and simultaneous condensation
4) Restriction: clean insulating parts
5) Average value, measured over 24 hours
6) Average value, measured over 1 month
U U
K
0
a
U Rated withstand voltage U under standard reference
atmosphere
U
Required rated withstand voltage for the installation
0
location
K
Altitude correction factor
a
m
(H - 1000)/8150
K
= e
a
Calculating the altitude correction factor K
H =
Installation altitude in metres
m = 1 for AC voltage, lightning impulse withstand
voltage (between phases, phase-to-earth, applied
longitudinally)
Example
For a required rated withstand voltage of 75 kV at an
altitude of 2,500 m, an insulation level of at least 90 kV
under standard reference atmosphere conditions is
required:
1
(2500 - 1000)/8150
90 kV 75 kV e
75 kV 1.2
Class
1)
3K4
,
2)
3K6
,
3Z2,
3Z5
3B1
3M2
3)
3C2
4)
3S2
:
a
9229 9992 176 0D
2013-07-08