Working Mode Settings - Xinje XP3-BD series Hardware Manual

14 bits input, 2 channel voltage 0/10-0/15 2 channel t temperature testing. 2 channel input, 2 channel output. 2 groups of pid parameter. 14/10 bits high precision analog output. 2 channel voltage 0/10v or0/5v
Table of Contents

Advertisement

4-5 Working mode settings

1) Expansion's input cards have voltage 0/5V,
0/10V these two modes and filter form to
select. Set via special FLASH data register
FD8306 in PLC. Refer to the graph by the
right; each register set the 4 channels' modes,
each register has 16 bits. From low bit to high
bit, each 4 bits set one channel's mode
Register FD8306:
Bit7
Bit6
00: 1/2 filter
01: not filter
10: 1/3 filter
11: 1/4 filter
Bit15
Bit14
00: 1/2 filter
01: not filter
10: 1/3 filter
11: 1/4 filter
2) Output channel's mode setting value is stored in register FD8307 (Low bit); its definition is
XP3-BD User Manual
CH 1
Bit5
Bit4
-
-
CH 3
Bit13
Bit12
0:0~10V
-
1:0~5V
Page 26 of 30
FD8306 H O O O O
CH 0
Bit3
Bit2
00: 1/2 filter
01: not filter
10: 1/3 filter
11: 1/4 filter
CH 2
Bit11
Bit10
00: 1/2 filter
01: not filter
10: 1/3 filter
11: 1/4 filter
0CH
1CH
2CH
3CH
Bit1
Bit0
-
-
Bit9
Bit8
0:0~10V
-
1:0~5V
MANUL008R2V1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Xp3-2ad2pt-bdXp3-2tc-p-bdXp3-2ptad1da-bd

Table of Contents