4-2 Specs
Item
Voltage Input
DC: 0to 5V, 0 to 10V
Analogue
(Input Resistance
Input Signal
300kΩ)
Digital Input
band
Analogue
Output band
Temperature
Testing
band
Distinguish
0.15mV 10/16383
Ratio
Digital Output
0 to 16383
band
Integrate
±0.8% of the full scale
Precision
Conversion
15ms × 4 channels
Time
PID output
0 to K4095
value
Vacant
defaulted
0
value
Input/output
Specialty
No isolation among PLC's each channel
Isolation
0 point (because it is operated via data register, so it is not limited by
Used I/O
master PLC's standard I/O control points)
XP3-BD User Manual
Temperature Input
Platinum resistor PT100
(2-wire format)
-100 to 350°C
0.1ºC
-1000 to 3500
3500
Page 23 of 30
D/A output
10 bits Binary
(0/1023)
0/20mA, 4/20mA
1/1023
MANUL008R2V1