Model 5496 Intelligent Power Module Installation and Operation Manual
3.2

Battery Connection

The 5496 battery charge capacity is 7.0 AH not to exceed 35.0 AH. Use 12V batteries
of the same AH rating. It is recommended that you replace batteries every five years.
Determine the correct AH rating per your current load calculation (see Table 2-4).
Note: If you require the power of back up batteries that are too large for the 5496, you can use the RBB
cabinet. The RBB Remote Battery Box, holds batteries up to the 35 AH size. (Refer to P/N 151306
for RBB installation instructions.
Wire batteries in series to produce a 24-volt equivalent. Do not parallel batteries to
increase the AH rating.
UL Listed 12V Battery
To Panel
Red
Black
Battery Jumper
(P/N 140694)
Shipped With 5496
Gell Cell
Replace batteries every 5 years.
Figure 3-2 Battery Connection
3-2
Supervised
Non-Power Limited
UL Listed 12V Battery
Gell Cell
151276-L8