151276-L8
Rechargeable
Battery Size
18 AH
35 AH
*
Required for NFPA 72 Auxiliary Protected Fire Alarm systems for Fire Alarm Service (City Box) and Remote Station
Protected Fire Alarm systems (Polarity Reversal) and Digital Alarm Communicator/Transmitter (DACT).
Note: 33 max battery size for FM (Factory Mutual) installations
Table 2-3: Maximum Battery Standby Load
Max. Load for 24 hrs. Standby,
5 mins. Alarm
685 mA
1370 mA
2-5
Before You Begin Installing
*Max. Load for 60 hrs. Standby, 5
mins. Alarm
270 mA
540 mA