Activation / Deactivation / Reset - Siemens FT2080 Operation Manual

Fire terminal (touch)
Hide thumbs Also See for FT2080:
Table of Contents

Advertisement

5
Operation

Activation / Deactivation / Reset

5.5 Activation / Deactivation / Reset
124
Building Technologies
Fire Safety
'Manned operation' / 'Unmanned operation' mixed operation
If one PMI has visibility to more than one fire control panel, with different 'Manned
operation' / 'Unmanned operation' operation modes, this is considered "mixed
operation".
Mixed operation: LED indicator 'Premises manned'
When there is at least one 'Premises manned' event, the 'Premises manned' LED
is on.
Mixed operation: Display button 'Manned/unmanned states'
When there is at least one 'Manned operation' event, the button shows the symbol
for 'Manned operation'.
By means of configured switching from 'Manned operation' to 'Unmanned
operation' at predefined times, the operation mode may switch although no
manual switching has been performed.
There is no possibility of an automatic switching from 'Unmanned operation' to
'Manned operation'.
You can activate and deactivate outputs, for example 'Sounders'.
Channel inputs, e.g. detectors, may be activated but not deactivated. These can be
reset after activation.
When 'Fire controls' is activated, this triggers smoke dampers, elevators, system
equipment, and extinguishing equipment (including those with extinguishing
gases), for example. You must take appropriate measures to prevent any possible
damage.
WARNING
Deactivated controls hinder appropriate measures in case of fire!
Personal injury and damage to property in the event of a fire.
Deploy staff to monitor the deactivated area.
You must reactivate deactivated controls as soon as possible.
WARNING
Activated parts of the ↑ site may actuate alarming and fire control!
Personal injury resulting from extinguishing activation.
The fire brigade is called up unnecessarily.
Set the 'Fire controls' to 'Control test' in advance.
Inform the fire brigade in advance.
A6V10380629_en--_a
2015-09-10

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents