Chapter 4: "SETPOINTS" Menu
4.6
Setpoint page 6: DIGITAL INPUTS
SETPOINT PAGE 6
DIGITAL INPUTS
INPUT 1 FUNCTION
BREAKER EARTHED
INPUT 1 ACTIVE
WHEN: CLOSED
INPUT 2 FUNCTION
EXTERNAL RESET
INPUT 2 ACTIVE
WHEN: CLOSED
INPUT 3 FUNCTION
NONE
INPUT 3 ACTIVE
WHEN: CLOSED
END OF PAGE
4.7
Setpoint page 7: EVENT RECORDER
SETPOINT PAGE 7
EVENT RECORDER
Gnd. PROTECTIONS
EVENTS: ON
SYSTEM ALARM
EVENTS: ON
OUTPUT RELAYS
EVENTS: ON
CURRENT PROTECTION RELAY - IPR-D
This PAGE allows setting the digital inputs.
RANGE:
.................................
Select the function to be associated with INPUT 1.
RANGE:
..........................................................................................
Configure digital input INPUT 1:
CLOSED ⇒ INPUT 1 will be active when the related contacts are closed.
OPENED ⇒ INPUT 1 will be active when the related contacts are open.
RANGE:
.................................
Select the function to be associated with INPUT 2.
RANGE:
..........................................................................................
Configure digital input INPUT 2:
CLOSED ⇒ INPUT 2 will be active when the related contacts are closed.
OPENED ⇒ INPUT 2 will be active when the related contacts are open.
RANGE:
.................................
Select the function to be associated with INPUT 3.
RANGE:
..........................................................................................
Configure digital input INPUT 3:
CLOSED ⇒ INPUT 3 will be active when the related contacts are closed.
OPENED ⇒ INPUT 3 will be active when the related contacts are open.
Last LINE of PAGE 6.
Press LINE or ▲PAGE, to pass to the first line of PAGE 7.
This PAGE allows to enable/disable the recording of the events, up to 10 max., according
to FIFO (First-In, First-Out) mode. Once 10 events are stored, the oldest event is cleared
by the new one occurred.
RANGE:
.................................................................................................................
It enables/disables ground current protection events recording.
RANGE:
.................................................................................................................
It enables/disables alarms events recording.
RANGE:
.................................................................................................................
It enables/disables output contacts events recording.
4.7
NONE; BREAKER EARTHED; EXTERNAL RESET;
REMOTE TRIP; BLOCK TRIP; ACTIVATE AUX1;
ACTIVATE AUX2; ACTIVATE AUX3
NONE; BREAKER EARTHED; EXTERNAL RESET;
REMOTE TRIP; BLOCK TRIP; ACTIVATE AUX1;
ACTIVATE AUX2; ACTIVATE AUX3
NONE; BREAKER EARTHED; EXTERNAL RESET;
REMOTE TRIP; BLOCK TRIP; ACTIVATE AUX1;
ACTIVATE AUX2; ACTIVATE AUX3
Manual P/N: IPR-D GBM 01/09/2006
CLOSED; OPENED
CLOSED; OPENED
CLOSED; OPENED
ON; OFF
ON; OFF
ON; OFF