ORION ITALIA IPR-D Instruction Manual page 10

Ground protection relay
Table of Contents

Advertisement

ENVIRONMENTAL FEATURES
The relay must be installed in a room with the following
features:
- indoor,
- dry, not dusty and not corrosive atmosphere.
CONSTRUCTION
In compliance with VDE, UL, CEI standards.
DIGITAL INPUT
Type:
Dry contacts
Output:
24 Vdc, 10 mA (stabilized)
COMMUNICATION
Type:
1 4-wire RS232 port + 2 2-wire RS485
ports, Full duplex, 1200÷19200 baud
Protocol:
Modbus RTU
Functions:
Reading/Writing of setpoints
Reading of actual values
Executing of commands
FRAME
Auto-extinguishing ABS with frontal in polycarbonate (IP54).
DIMENSION
144 x 144 x 141 mm (→ Fig. 2.1 – IPR-D overall dimensions)
WEIGHT
1.5 Kg
GROUND CT INPUT
Secondary rated current: CT: 1 A or 5 A (specify with order).
Sampling:
True RMS at 16 samples per
cycle.
Bandwidth:
0÷100 Hz
CT burden:
0.25 VA at rated secondary
current.
Continuous:
10 A
Current withstand capacity:
INVERSE-TIME GROUND OVERCURRENT
(51G/51N)
Pickup level:
4÷300% CT, Steps: 1%
Time multiplier:
0.1÷20.0; Steps: 0.1
Dropout level:
Time
current level drops below the pickup
level.
Current accuracy:
± 3% of the setting.
Time accuracy:
included in ± 3% or in ±20 ms, per
>150% of the set value.
CURRENT PROTECTION RELAY - IPR-D
100 A per 1 s
resets
to
zero
whenever
OUTPUT CONTACT
Load:
resistive (p.f.= 1)
inductive (p.f.= 0.4; L/R = 7 ms)
Rated load:
250 Vac, 8 A or 30 Vcc, 8 A with p.f.=1
250 Vac, 5 A or 30 Vcc, 5 A with p.f.=0.4
Max. operating Voltage: 250 Vac, 125 Vcc
Max. operating Current: 8 A
Capacity:
2000 VA, 240 W with p.f.=1
1250 VA, 150 W with p.f.=0.4
LED INDICATORS
Relay status:
Trip, Alarm, Service
System status:
Closed circuit breaker, open circuit
breaker, earthed circuit breaker and
reaching of:
Pickup level I
Pickup level I
Display (LCD):
16 x 2 digits
Display accuracy:
Load current:
TERMINAL BLOCK
Fixed, for cables with section: 4 mm
MOUNTING
The relay has to be jointed to the structure fixing it by stirrup
with screws.
FRONT PANEL CUT-OUT
137 x 137 mm
APPLICABILITY
System:
Frequency:
Current:
Voltage:
OVERCURRENT CURVES
Selection of ground curves according to ANSI, IAC or IEC.
Moderately inverse
Normally inverse
Extremely inverse
Definite time
The curves are valid up to 18 times the CT rated current
GROUND INSTANTANEOUS OVERCURRENT
(50G/50N)
Pickup level:
Current accuracy:
Time accuracy:
Saturation:
1.4
Chapter 1: General information
> (51N/G)
0
>> (50N/G)
0
±1% @ 100% CT
2
(12 AWG).
three-phase;
50 and 60 Hz;
max. 5000 A;
max. 69 kV
4÷1800% of CT, Steps: 10%
± 3% of the set value.
35 ms max. per > 150% of the set
pickup level.
18 times the CT rated current.
Manual P/N: IPR-D GBM 01/09/2006