Allen-Bradley CompactLogix 5380 Installation Instructions Manual page 9

Hide thumbs Also See for CompactLogix 5380:
Table of Contents

Advertisement

3. Connect the 24V DC(+) wire from the external power supply
to the first MOD(+) terminal.
RTB Type
Action
1. Insert the wire into the terminal.
Screw
2. Turn the screwdriver to close the terminal on the wire. Torque the
screw to 0.4 N•m (3.5 lb•in).
Push the wire into the terminal.
Spring
If necessary, you can crimp a wire ferrule on the wire and insert it.
5069-RTB4-SCREW RTB
4. Connect the 24V DC(—) wire from the external power supply
to the first MOD(—) terminal.
RTB Type
Action
1. Insert the wire into the terminal.
Screw
2. Turn the screwdriver to close the terminal on the wire. Torque the
screw to 0.4 N•m (3.5 lb•in).
Push the wire into the terminal.
Spring
If necessary, you can crimp a wire ferrule on the wire and insert it.
5069-RTB4-SCREW RTB
Install the SA Power RTB
WARNING: If you connect or disconnect the Removable Terminal
Block (RTB) with power applied, an electrical arc can occur. This
could cause an explosion in hazardous location installations.
The Removable Terminal Block (RTB) does not support "Removal
and Insertion Under Power" (RIUP) capability. Do not connect or
disconnect the Removable Terminal Block (RTB) while power is
applied. Be sure that power is removed before proceeding.
1. Hook the bottom of the SA power RTB on the controller.
5069-RTB4-SPRING RTB
Connect SA DC Power
Before you connect an external DC power source to the SA power
RTB, make sure that the SA power source is adequately sized.
5069-RTB4-SPRING RTB
RTB Type
Screw
Spring
RTB Type
Rockwell Automation Publication 5069-IN013D-EN-P - April 2018
2. Push the RTB against the controller until you hear a click.
3. Push the RTB handle against the RTB until you hear a click.
WARNING: If you connect or disconnect wiring while the field-
side power is on, an electrical arc can occur. This could cause an
explosion in hazardous location installations. Be sure that power is
removed or the area is nonhazardous before proceeding.
1. Confirm that MOD power and SA power sources are
turned off.
2. Strip insulation from the wires that you connect to the RTB.
Action
Strip12 mm (0.47 in) of insulation from the wires.
Strip 10 mm (0.39 in) of insulation from the wires.
3. Connect the DC(+) wire from the external DC power supply
to the first SA(+) terminal.
Action
1. Insert the wire into the terminal.
Screw
2. Turn the screwdriver to close the terminal on the wire. Torque the
screw to 0.4 N•m (3.5 lb•in).
Push the wire into the terminal.
Spring
If necessary, you can crimp a wire ferrule on the wire and insert it.
5069-RTB6-SCREW RTB
CompactLogix 5380 Controllers
SA Power RTB
5069-RTB6-SPRING RTB
9