CompactLogix 5380 Controllers
IEC Hazardous Location Approval
The following applies to products with IECEx certification:
• Are intended for use in areas in which explosive atmospheres caused by gases, vapors, mists, or air are unlikely to occur, or are likely to occur only infrequently and for short
periods. Such locations correspond to Zone 2 classification to IEC 60079-0.
• The type of protection is "Ex nA IIC T4 Gc" according to IEC 60079-15.
• The CompactLogix 5380 controllers comply to standards IEC 60079-0:6th Edition, IEC-60079-15:4th Edition when used at or below 125V AC, reference IECEx certificate
number IECEx UL 15.0007X.
• May have catalog numbers followed by a "K" to indicate a conformal coating option.
WARNING: Special Conditions for Safe Use:
• This equipment is not resistant to sunlight or other sources of UV radiation.
• This equipment shall be mounted in an ATEX/IECEx Zone 2 certified enclosure with a minimum ingress protection rating of at least IP54 (as defined in
EN/IEC 60529) and used in an environment of not more than Pollution Degree 2 (as defined in EN/IEC 60664-1) when applied in Zone 2 environments. The
enclosure must be accessible only by the use of a tool.
• This equipment shall be used within its specified ratings defined by Rockwell Automation.
• Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 140 % of the rated voltage when applied in
Zone 2 environments.
• The instructions in the user manual shall be observed.
• Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this
product.
• Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
• Earthing is accomplished through mounting of controllers on rail.
• Devices shall be used in an environment of not more than Pollution Degree 2.
• The USB port is intended for temporary local programming purposes only and not intended for permanent connection. Do not use the USB port in hazardous
locations.
Prevent Electrostatic Discharge
ATTENTION: This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when
you handle this equipment:
• Touch a grounded object to discharge potential static.
• Wear an approved grounding wriststrap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• Use a static-safe workstation, if available.
• Store the equipment in appropriate static-safe packaging when not in use.
ATTENTION:
• In case of malfunction or damage, no attempts at repair should be made. The controller should be returned to the manufacturer for repair. Do not dismantle
the controller.
• This equipment is certified for use only within the surrounding air temperature range of 0...60 °C (32...140 °F). The equipment must not be used outside of
this range.
• The USB port is intended for temporary local programming purposes only and not intended for permanent connection. The USB cable is not to exceed 3.0 m
(9.84 ft) and must not contain hubs.
• Use only a soft dry anti-static cloth to wipe down equipment. Do not use any cleaning agents.