About The Controller; Required System Components - Allen-Bradley CompactLogix 5380 Installation Instructions Manual

Hide thumbs Also See for CompactLogix 5380:
Table of Contents

Advertisement

WARNING:
• If you connect or disconnect wiring while the field-side power is on, an electrical arc can occur. This could cause an explosion in hazardous location
installations. Be sure that power is removed or the area is nonhazardous before proceeding.
• When you insert or remove the SD memory card while power is on, an electrical arc can occur. This could cause an explosion in hazardous location
installations. Be sure that power is removed or the area is nonhazardous before proceeding.
• When you press the reset button while power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that
power is removed or the area is nonhazardous before proceeding.
• When you change switch settings while power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that
power is removed or the area is nonhazardous before proceeding.
WARNING: Do not use the USB port in hazardous locations.
Any illustrations, charts, sample programs, and layout examples that are shown in this publication are intended solely for the purposes of example. Since
IMPORTANT
there are many variables and requirements that are associated with any particular installation, Rockwell Automation does not assume responsibility or
liability for actual use that is based upon the examples that are shown in this publication.

About the Controller

The following graphic shows a CompactLogix 5380 controller.
DIN Rail Latches
Four-character
Display
Status Indicators
SD Card Slot
Mode Switch
Reset Button
USB Port
Ethernet ports (bottom of controller)

Required System Components

Before you install the controller, verify that you have the
following components.
Module Power and
Components Needed to Install a CompactLogix 5380 Controller
Sensor/Actuator
Power Status
Component
Indicators
MOD Power RTB
MOD Power Bus
Connector
Removable
Terminal Blocks
(RTB)
SA Power RTB
SA Power Bus
Connector
External power
supply for
Module (MOD)
Power
Rockwell Automation Publication 5069-IN013D-EN-P - April 2018
CompactLogix 5380 Controllers
Description
One of the following RTB types for each power type:
MOD Power (system-side power)
SA Power (field-side power)
• 5069-RTB4-SCREW RTB
• 5069-RTB6-SCREW RTB
• 5069-RTB4-SPRING RTB
• 5069-RTB6-SPRING RTB
IMPORTANT: RTBs do not ship with CompactLogix 5380 controllers. You
must order RTBs separately.
The RTBs are available in 5069 RTB kits. The 5069-RTB64-SCREW kit
contains the 5069-RTB6-SCREW and 5069-RTB4-SCREW RTBs. The 5069-
RTB64-SPRING kit contains the 5069-RTB6-SPRING and 5069-RTB4-SPRING
RTBs. We recommend that you order only the RTB type that your system
requires.
A power supply that is adequately sized to provide MOD power, that is,
system-side power, to the CompactLogix 5380 system.
For more information, see
System Power Considerations on page
7.
5