16 Specifications
Physical
Size (unit with Sensor cartridge)
Weight (unit with Sensor cartridge)
NF
Pyrolyzer Dimensions
3
Size
Weight
High-Temperature PFC Pyrolyzer Dimensions
Size
Weight
0
P
3
Pyrolyzer Dimensions
Size
Weight
Power Requirements:
Operating Voltage
Operating Voltage with Power over
Ethernet
Power Consumption:
Transmitter unit
Transmitter with pyrolyzer (std or hi temp) < 12.95 W
Transmitter with LonWorks Module
Transmitter with LonWorks and pyrolyzer
Outputs:
Visual
Relays
Analog
Digital Communications
Service Port
150 mm(H) x 65 mm(W) x 153 mm (D) (5.91 x 2.56 x 6.02 in)
0.8 kg (1.76 lb)
70 mm (H) x 63 mm (W) x 85 mm (D) (2.75 x 2.48 x 3.35 in)
0.41 kg (0.9 lb)
100 mm (H) x 101 mm (W) x 140 mm (D) (3.9 x 4.0 x 5.5 in)
1.36 kg (3.0 lb)
132 mm (H) x 60 mm (W) x 98 mm (D)
1.20Kg (2.65 lb)
24 V Nominal -15 to +10% (20.4 to 26.4 VDC)
Midas
pyrolyzers and Midas
®
restricted minimum voltage requirement of 21.6 VDC.
48 VDC Power-over-Ethernet (IEEE 802.3af compliant)
< 5 W
< 8 W
< 15.95 W
Alarm, power and fault LEDs plus LCD with all gas readings and events.
Alarm1, Alarm2, Fault Relays (3) rated 1.0 A @ 30VDC or 0.5 A @ 125 VAC max
10 uA @ 10 mV minimum, configurable as normally open or closed, latched or
unlatched.
3 wire sink, 3 wire source, or 4 wire fully isolated; 0 to 21 mA.
Modbus / TCP Ethernet / Power over Ethernet (PoE) / LonWorks
Module
RS232C / PPP protocol
16-2
Midas
Gas Detector
®
Transmitters with LonWorks Modules have a
®
Interface
®

Hide quick links: