Enable Object "Error Code [2Byte]; Enable Object "Error Text Code [14Byte] - IntesisBox ME-AC-KNX-1i User Manual

Table of Contents

Advertisement

KNX – Mitsubishi Electric A.C.
®
IntesisBox
If set to "yes" the Status_ Operation Hour Counter object will appear.
o
This object can be read and sends its status every time an hour is counted.
The gateway keeps that count in memory and the status is sent also after a
KNX bus reset/failure. Although this object is marked as a Status_ object it
also can be written to update the counter when needed. To reset the counter
should be written a "0" value.
Important: This object comes by default without the write (W) flag
activated. If is necessary to write on it, this flag must be activated.
Important: This object will also return its status, every time a value is
written, only if it's different from the existing one.
Important: If the stored value is 0 hours, the gateway will not send the
status to KNX.

4.1.6 Enable object "Error Code [2byte]"

This parameter shows/hides the Status_ Error Code communication object which shows the
indoor unit errors, if occurred, in numeric format.
If set to "no" the object will not be shown.
o
If set to "yes" the Status_ Error Code [2byte] object will appear.
o
This object can be read and also sends the indoor unit error, if occurred, in
numeric format. If a "0" value is shown that means no error.

4.1.7 Enable object "Error Text Code [14byte]"

This parameter shows/hides the Status_ Error Text Code communication object which
shows the indoor unit errors, if occurred, in text format.
If set to "no" the object will not be shown.
o
If set to "yes" the Status_ Error Text Code object will appear.
o
This object can be read and also sends the indoor unit error, if occurred, in
text format. The errors shown have the same format as at the remote
controller and at the error list from the indoor unit manufacturer. If the
object's value is empty that means no error.
© Intesis Software S.L.U. - All rights reserved
This information is subject to change without notice
®
IntesisBox
is a registered trademark of Intesis Software SLU
User's manual r2.3 eng
URL
http://www.intesisbox.com
Email
info@intesisbox.com
tel
+34 938047134
12 / 63

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ME-AC-KNX-1i and is the answer not in the manual?

Subscribe to Our Youtube Channel

Table of Contents