Installation; Dip Switch Settings - LEGRAND Wattstopper PW-203 Installation Instructions Manual

Passive infrared multi-way dual relay wall switch occupancy sensor v3
Table of Contents

Advertisement

Available languages

Available languages

1. Make sure that the power has been turned OFF at the circuit breaker.
2. Connect wires to the PW flying leads as shown in the wiring diagram.
The ground wire (green) must be fastened to ground for the
sensor to work properly.
3. Attach the sensor to the wall box by inserting screws into the two wide holes on the top and bottom of the attached metal bracket.
Match them up with the holes in the wall box and tighten.
4. Turn the circuit breaker ON. Wait one minute, then push the Auto ON/OFF switch for each load and the lights will turn ON. There
is a delay due to initial power-up of the sensor that only occurs during installation.
5. Test and adjust the sensor if necessary.
6. Attach the cover plate.
Important: Wire the remote unit to the same branch circuit as the main unit controlling the load. If Relay 2 of the main
unit cannot be controlled from the remote unit, check wiring to be sure both units are on the same branch circuit.
PW-203
1 2 3
Time Delay
Test/20 min
5 minutes
10 minutes
15 minutes
20 minutes
25 minutes
30 minutes
Service
4
Walk-Through
Enabled
Disabled
Service bypasses occupancy
& light level functions. Control the
load manually using ON/OFF button.
DIP Switch Adjustments
Remove the wall plate. Remove the button cap by firmly squeezing together the top sides of the button assembly. Gently pull it away
from the unit.
When the adjustments are completed, replace the button cap by inserting its hinges into the tabs on the main unit and then squeeze the
top of the button while pressing it into the unit. Reinstall the cover plate.
Junction Box
White (Neutral)
Black (Line)
Blue (Line)
Red (Load 1)
Brown (Load 2)
Yellow (Traveler)
Ground
Relay 1 Mode
Time
Visible
Relay 2 Mode
Delay
Alerts
ON
1
2
3
4
5
6
7
8
9
Walk-Through
Audible Alerts
PIR Sensitivity
5
PIR Sensitivity
Low, 50%
High
6
Visible Alert
Enabled
Disabled
=ON
=OFF

INSTALLATION

Load 2
2
Load 1
1

DIP SWITCH SETTINGS

7
Audible Alert
Enabled
Disabled
8
Relay 1 Mode
Manual On
Button
Hinges
Auto On
9
Relay 2 Mode
Manual On
Auto On
=Factory Setting
ADJUSTMENTS
3
WARNING: TURN THE POWER OFF AT THE
CIRCUIT BREAKER BEFORE WIRING.
120/277V 50/60Hz
White (Neutral)
Black (Line)
Junction Box
Tabs
#12 – #14 AWG
Strip Gauge
1/2"
12.7mm
Cu Wire Only
PW-203
ON/OFF Buttons
Relay 1
Relay 2
DIP Switches
Detection LED