LEGRAND Wattstopper PW-311-I Installation Instructions Manual

LEGRAND Wattstopper PW-311-I Installation Instructions Manual

Passive infrared 0–10 volt wall switch occupancy sensor
Table of Contents

Advertisement

Available languages

Available languages

Quick Links

No: 29109 – 09/20 rev. 1
Catalog Numbers • Les Numéros de Catalogue • Números de Catálogo: PW-311
Country of Origin: Made in China • Pays d'origine: Fabriqué en Chine • País de origen: Hecho en China
Models ending in -U are BAA and TAA compliant (Product produced in the U.S.)
The PW Passive Infrared Wall Switch sensors use advanced passive infrared (PIR) technology.
• PW sensors have Multi-Way available on all models.
• A "walk-through" mode can turn lights off after only 3 minutes, if no activity is detected after 30 seconds following an occupancy
detection.
• The PW-311 has one relay with dimming control capability and two buttons to allow control of the dimming.
• PW sensors contain a light level sensor. If adequate daylight is present, the sensor holds the load OFF until light levels drop, even
if the area is occupied. See the Light Level Adjustment section.
• On loss of normal power to the PW-311, the 0-10V dimming control will open. Any light fed with a separate circuit but controlled by
the unit's 0-10V signal will go to 100%.
1. Make sure that the power has been turned OFF at the circuit breaker.
2. Connect wires to the PW flying leads as shown in the wiring diagram that
is appropriate to the PW model and electrical supply. The ground wire
(green) must be fastened to ground for the sensor to work properly.
3. Attach the sensor to the wall box by inserting screws into the two wide
holes on the top and bottom of the attached metal bracket. Match them up with the
holes in the wall box and tighten. Do not use excessive force when installing the
sensor into the wallbox. Doing so can bend the mounting strap which can affect button
operation.
4. Turn the circuit breaker ON. Wait one minute, then push the Auto ON/OFF switch
and the lights will turn ON. There is a delay due to initial power-up of the sensor that
only occurs during installation.
5. Test and adjust the sensor if necessary.
6. Install industry standard decorator wall switch cover plate (not included).
WARNING: Grounding the violet and gray wires can damage the unit. Do not apply power
to the sensor until all wires are connected or capped off if the driver is to be installed at a
future time.
Signal Wire (Blue with White Stripe) connects to Neutral. For a replacement or retrofit application , it can connect to Ground.
Wattstopper
Passive Infrared 0–10 Volt Wall Switch Occupancy Sensor (Version 2)
Interrupteur mural 0–10 Volt avec détecteur de mouvement à infrarouges passif (v2)
Sensor de ocupación con interruptor de pared y tecnología de infrarrojo pasivo de
voltaje 0 a 10 (v2)
Installation Instructions • Instructions d'Installation • Instrucciones de Instalación
Voltages ......................................................120/240/277 VAC, 50/60 Hz
Load Limits:
@120 VAC ........... 1000-W tungsten ballast, E-ballast, LED, 1/4 HP
@240/277 VAC ............... 1200-W ballast, E-ballast, LED, 1/4 HP
Time Delay Adjustment ..................................................3 to 30 minutes
Walk-Through Mode ....................... 3 minutes if no activity after 30 sec.
Test Mode ............................................. 10 min. with 10-sec. time delay
PIR Adjustment .................................................................... High or Low
Light Level Adjustment .......................................................8fc to 180+fc
Alerts ........................................................Selectable Audible & Visual
Terminal screw torque ............................................ 16 lbf-in (18 kgf-cm)
High Trim .................................................................................. 6 to 10 V
Low Trim ..................................................................................... 0 to 4 V
Ramp Up ....................................................................... 1 to 10 seconds
Fade Down ................................................................. 2.5 to 30 seconds
Signal Wire
Multi-Way Capability
DESCRIPTION
INSTALLATION
®
SPECIFICATIONS
WARNING: TURN THE POWER OFF AT
THE CIRCUIT BREAKER BEFORE WIRING.
Yellow
Black
Line
Green
Ground
Neutral
0 a 10V
Dimming
Violet
Driver
Gray
or Ballast
Red
Signal
(Blue w/
White
Stripe)

Advertisement

Table of Contents
loading

Summary of Contents for LEGRAND Wattstopper PW-311-I

  • Page 1 Wattstopper ® Passive Infrared 0–10 Volt Wall Switch Occupancy Sensor (Version 2) Interrupteur mural 0–10 Volt avec détecteur de mouvement à infrarouges passif (v2) Sensor de ocupación con interruptor de pared y tecnología de infrarrojo pasivo de No: 29109 – 09/20 rev. 1 voltaje 0 a 10 (v2) Installation Instructions •...
  • Page 2: Button Functions

    MULTI-WAY The Multi-Way capability is available on all models. Sensors can Typical Multi-way Wiring (Up to 4 sensors) easily be wired together for convenient control of a common load. When wiring this way, only use 311 series sensors. Multi-Way in Connect 0-10V Line leads to dimming...
  • Page 3 Auto ON With DIP switch 1 in the OFF position, the load turns ON and OFF automatically based on occupancy. There is a 5 second re-trigger delay. If the load is turned OFF manually, the enable/disable setting for Presentation Mode operation applies. See Presentation Mode / Disable Presentation Mode for details.
  • Page 4 Light Level Adjustment This features allows you to set a light level threshold, which determines how the PW-311 will respond based on the ambient light level. This function is available only when the PW-311 is set for Auto ON. There are two modes of Light Level Adjustment. In the Standard mode, you set a fixed threshold. The load will not turn ON automatically until the ambient light drops below that threshold.
  • Page 5: Dip Switch Settings

    DIP SWITCH SETTINGS Time Additional Additional Features Green LED # of Blinks Delay Features Exit Programming Mode Visual Alert 1=OFF, 2=ON Audio Alert 1=ON, 2=OFF Walk-Thru 1=OFF, 2=ON Mode PIR Sensitivity 1=100%, 2=50% Unused High Trim 1=10V, 2=Manual Adjustment Low Trim 1=0V, 2=Manual Adjustment Mode Manual - On...
  • Page 6: Installation

    INSTRUCTIONS EN FRANÇAIS DESCRIPTION DE L’APPAREIL CARACTÉRISTIQUES TECHNIQUES Les interrupteurs muraux avec détecteur de mouvement à Tensions .............120/240/277 V c.a., 50/60 Hz infrarouge passif PW utilisent technologie de pointe pour Charge nominale : l’infrarouge passif (IRP). à 120 V c.a..ballast tungstène 1 000 W, ballast électronique, DEL, 1/4 HP •...
  • Page 7: Fonctions Des Boutons

    MULTI-VOIES Multi-voies câblage standard La fonction de multi-voies est disponible sur tous les modèles. Les (jusqu'à 4 détecteurs) détecteurs peuvent facilement être connectés les uns aux autres pour le contrôle pratique d’une même charge. Si vous effectuez ce type Le raccordement de câblage, utilisez uniquement des détecteurs de la série 311.
  • Page 8 RÉGLAGE DU DÉTECTEUR ET ACCÈS AUX FONCTIONNALITÉS SUPPLÉMENTAIRES Retirez la plaque murale. Retirez le cache des boutons en serrant fermement et Bouton d'augmentation lumineuse simultanément les parties supérieures de l’assemblage des boutons. Retirez-le Bouton de diminution doucement de l’appareil. lumineuse Une fois les réglages terminés, reposez le cache des boutons en insérant ses charnières dans les ergots de l’unité...
  • Page 9 Mode passage Le mode passage raccourcit la temporisation pour réduire le délai d’ACTIVATION de la charge après une brève présence, telle qu’un retour au bureau pour récupérer un objet oublié suivi d’une sortie immédiate. Si le mode passage est ACTIVÉ, le capteur PW COUPE la charge trois minutes après la première détection de présence si aucun mouvement n’est détecté...
  • Page 10 Mode présentation / Désactiver le mode présentation Le mode présentation est une fonctionnalité du mode MARCHE automatique. Lorsque le relais est COUPÉ manuellement, le PW maintient les lumières ÉTEINTES jusqu’à ce que plus aucun mouvement ne soit détecté pendant la durée de la temporisation. Si une présence est détectée par la suite, le PW ACTIVE la charge.
  • Page 11: Dépannage

    DÉPANNAGE Les lumières ne S’ALLUMENT pas lorsqu’il y a du mouvement (la DEL clignote). 1. Enfoncez puis relâchez chaque bouton pour vous assurer que les bonnes lumières S’ALLUMENT pour chaque relais. Si les lumières ne S’ALLUMENT PAS, vérifiez le raccordement des fils, notamment le raccordement de la charge. Si les lumières S’ALLUMENT, vérifiez que le bon mode de marche est sélectionné...
  • Page 12: Instalación

    INSTRUCCIONES EN ESPAÑOL DESCRIPCIÓN DE LA UNIDAD ESPECIFICACIONES Los sensores con interruptor de pared PW utilizan Voltajes ................. 120/240/277 V CA, 50/60 Hz tecnología infrarroja pasiva (PIR) avanzada. Límites de carga: • Los sensores PW tienen múltiple vías en todos los A 120 V CA .
  • Page 13: Funciones Del Botón

    MÚLTIPLES VÍAS Cableado típico de múltiples vías La funcionalidad de múltiples vías está disponible en todos los (hasta 4 sensores) modelos. Los sensores pueden cablearse fácilmente en conjunto para un control conveniente de la carga común. Cuando cablee de Conecte los conductores esta manera, solo utilice sensores de la serie 311.
  • Page 14 AJUSTE DEL SENSOR Y ACCESO A OTRAS FUNCIONES Elimine la placa de la pared. Quite la tapa del botón apretando firmemente los Botón de aumento laterales superiores del botón de ensamble. Con cuidado, retírela de la unidad. Botón de atenuación Cuando se completen los ajustes, vuelva a colocar la tapa del botón insertando sus bisagras en las pestañas de la unidad principal y, luego, apriete la parte superior del botón mientras lo presiona hacia la unidad.
  • Page 15 Recorrido El modo de recorrido acorta el tiempo de demora para reducir la cantidad de tiempo en que la carga está encendida después de un breve momento de ocupación como, por ejemplo, volver a la oficina para buscar algo que se olvidó y salir inmediatamente. Si el modo de recorrido se enciende, el sensor PW apaga la carga tres minutos después de que el área esté...
  • Page 16 • Predeterminado a apagado: la carga permanece apagada después de que se restaura la alimentación. Modo de presentación / Modo de desactivación de presentación El modo de Presentación es una función del modo de Encendido automático. Cuando el relé se apaga manualmente, el PW mantiene las luces apagadas hasta que no se detecta ningún movimiento durante el tiempo de demora.
  • Page 17: Solución De Problemas

    No. 29109 – 09/20 rev. 1 © Copyright 2020 Legrand All Rights Reserved. 800.879.8585 © Copyright 2020 Tous droits réservés Legrand. www.legrand.us/wattstopper © Copyright 2020 Legrand Todos los derechos reservados.

This manual is also suitable for:

Wattstopper pw-311

Table of Contents