Group 7* - Lockout Settings - American Standard AccuLink Platinum 1050 Installation Manual

Communicating connected control
Hide thumbs Also See for AccuLink Platinum 1050:
Table of Contents

Advertisement

5.3.8 Group 7* - Lockout Settings

* If Zoning is enabled, this group will be called Group 8.
An Outdoor Temperature Sensor must be enabled for Lockout settings to be selectable.
MENU ITEM
Quiet Mode
Auxiliary Heat Lockout
Auxiliary Heat Lockout Setting
Compressor Heat Lockout
Compressor Heat Lockout Setting
Defrost Heater Balance Point (W1)
Defrost Heater Balance Point (W1) Setting
Defrost Heater Balance Point (W2)
Defrost Heater Balance Point (W2) Setting
Defrost Heater Balance Point (W3)
Defrost Heater Balance Point (W3) Setting
Compressor Cooling 1st Stage Lockout 1
Compressor Cooling 1st Stage Lockout Setting 1
Compressor Heating 1st Stage Lockout 12
Compressor Heating 1st Stage Lockout Setting 1
Furnace Heating 1st Stage Lockout 13
Furnace Heating 1st Stage Lockout Setting 1
1 This feature is not available when zoning is enabled
2 This feature is not available if Compressor Heat Lockout is enabled
3 This feature is not available if Aux Heat Lockout is enabled
4 See the "Dual Fuel Calculator" table for additional options when Enabled
Dual Fuel Calculator
SETTING
Select the type of Auxiliary (Back-up) Heat Installed
Enter electricity cost in $/kwh
Select Gas Option
Choose the furnace AFUE rating
Choose the Heat Pump HSPF rating
11-HD15D1-5-EN
OPTIONS
[DEFAULT]
[Disable], Enable
[Disable], Enable
32°F - 70°F Degrees
[45°F]
[Disable], Enable 4
5°F - 70°F Degrees
[30°F]
[Disable], Enable
40°F - [55°F]
[Disable], Enable
10°F - 50°F [55°F]
[Disable], Enable
[5°F] - 45°F
[Disable], Enable
80°F - [120°F]
[Disable], Enable
0°F - [50°F]
[Disable], Enable
0°F - [50°F]
OPTIONS
Gas Furnace, Oil Furnace
Electricity Cost
Natural Gas $/therm, Natural Gas $/MCF,
Natural Gas $/Gal
78 – 98
7.7 – 12
DESCRIPTION
Enables the installer to limit system operation (heating and cooling
mode) to meet local daytime and nighttime sound requirements, if
necessary.
Enable auxiliary heat lockout (10° minimum separation when enabling
auxiliary heat lockout and compressor heat lockout)
Select an outdoor temperature to prevent auxiliary heat above the
selected outdoor temperature
Enable compressor heat lockout (10° minimum separation when
enabling auxiliary heat lockout and compressor heat lockout)
When Enabled, another setting appears: Compressor Heating
(Auto OR Manual). 4 If Manual is selected, you can manually
select values. If Auto is selected, then a series of questions appear
to help you determine the most efficient switchover point.
Select an outdoor temperature to prevent compressor heating below the
selected outdoor temperature
Enable defrost heater balance point for W1 (only applicable when indoor
heat is electric or hydronic)
Select an outdoor temperature to disallow 1st stage of indoor heat during
defrost above this temperature
Enable defrost heater balance point for W2 (only applicable when indoor
heat is electric or hydronic)
Select an outdoor temperature to disallow 2nd stage of indoor heat
during defrost above this temperature
Enable defrost heater balance point for W3 (only applicable when indoor
heat is electric or hydronic)
Select an outdoor temperature to disallow 3rd stage of indoor heat
during defrost above this temperature
Enable compressor cooling 1st stage lockout
Select an outdoor temperature to force the system to 2nd stage
compressor cooling
Enable compressor heating 1st stage lockout
Select an outdoor temperature to force the system to 2nd stage
compressor heating
Enable furnace heating 1st stage lockout
Select an outdoor temperature to force the system to 2nd stage furnace
heating
DESCRIPTION
Select your indoor heat type
Enter what you currently pay per kilowatt of electricity (see most current electric
bill for current rate)
Enter what you currently pay for natural gas (see most current gas bill for current
rate)
Enter the AFUE rating of the installed furnace (If not known, estimate based on
the age of the furnace and the venting type. 90% - 98% for furnaces vented with
PVC vent, 80% for motor assisted vented furnaces with double-wall metal vent
and 50% - 60% for natural draft furnaces.)
Enter the HSPF rating of the installed heat pump. (see AHRI ratings)
Platinum 1050