Physical Data - York PCG6B36 Technical Manual

Single package air conditioner / gas heat 16 seer – r-410a – 208/230v - 3 phase 3 thru 5 nominal tons 65 - 125 mbh heat input
Hide thumbs Also See for PCG6B36:
Table of Contents

Advertisement

5291596-YTG-E-1117
GAS HEATING SECTION (If Equipped)
Heat exchanger and exhaust system shall be constructed of
corrosion-resistant materials and shall be designed with
induced draft combustion with post purge logic and redundant
main gas valve. The heat exchanger shall be of the tubular
type, constructed of stainless steel for corrosion resistance and
allowing minimum mixed air entering temperature of 40 ºF.
Burners shall be of the in-shot type, constructed of
aluminumized steel. All gas piping shall enter the unit cabinet at
a single location through either the side or bottom, without any
field modifications. An integrated control board shall provide
timed control of indoor fan functioning and burner ignition.

PHYSICAL DATA

NOMINAL TONNAGE
AHRI Cooling Performance
Gross Capacity @ AHRI A point (MBH)
AHRI net capacity (MBH)
EER
SEER
Nominal CFM
System power (KW)
Refrigerant type
Refrigerant charge (lb-oz)
AHRI Gas Heat Performance
Heating model
Heat input - High Fire (KBtu)
Heat output - High Fire (KBtu)
Heat input - Low Fire (KBtu)
Heat output - Low Fire (KBtu)
AFUE %
No. burners
No. stages
Temperature Rise Range - High Fire (° F)
Temperature Rise Range - Low Fire (° F)
Max. Static Pressure w.c.
Max. Outlet Air Temp. (° F)
Gas piping connection (in.)
Dimensions (inches)
Length
Width
Height
Compressor
Type
Stages
Outdoor Coil Data
Face area (Sq. Ft.)
Rows
Fins per inch
Tube diameter
Circuitry Type
Continued on next page.
6
PCG6B36
PCG6B42
3.0
3.5
36.5
43.3
36.0
42.5
12.5
12.5
16.0
16.0
1200
1400
3.0
3.4
R410A
R410A
11-8
11-4
65
100
65
65
100
65
52
81
52
43
65
43
34
53
34
81.0
81.0
81.0
2
3
2
2
2
2
40-70
40-70
25-55
25-55
0.5
0.5
180
180
1/2
1/2
51-1/4
51-1/4
45-3/4
45-3/4
49
49
Scroll
Scroll
2
2
19.5
19.5
2
2
22
22
3/8
3/8
Interlaced
Interlaced
Heating section shall be provided with the following minimum
protection:
a. Primary high-temperature limit switch.
b. Induced draft pressure switch.
c. Flame roll out switch(es) (manual reset).
d. Flame proving controls.
All gas heat models will meet the California requirement for
emissions of less than 40 nanograms per Joule (California
requirement on single phase models only).
MODELS
PCG6B48
4.0
49.1
45.5
12.0
16.0
1600
3.6
R410A
13-8
100
65
100
100
65
100
81
52
81
65
43
65
53
34
53
81.0
81.0
81.0
3
2
3
2
2
2
40-70
25-55
0.5
180
1/2
51-1/4
45-3/4
53
Scroll
2
23.8
2
22
3/8
Interlaced
PCG6B60
5.0
60.0
58.0
12.0
16.0
2000
4.6
R410A
14-0
125
65
100
125
65
100
101
52
81
82
43
65
66
34
53
81.0
81.0
81.0
4
2
3
2
2
2
40-70
25-55
0.5
180
1/2
51-1/4
45-3/4
55
Scroll
2
25.9
2
22
3/8
Interlaced
Johnson Controls Unitary Products
125
125
101
82
66
81.0
4
2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pcg6b42Pcg6b60Pcg6b48

Table of Contents