Zf180 Physical Data - York ZF Series Installation Manual

R-410a 15 ton/53 kw 50 hertz
Hide thumbs Also See for ZF Series:
Table of Contents

Advertisement

5326601-XIM-A-0117
Table 10: ZF180 Physical Data
Component
Nominal Tonnage
Brand
Country of Origin
Rated Voltage Range
Rated Frequency
Nominal CFM
Rated Cooling Capacity (T1) - BTUH
Rated Power Input (T1) - KW
Energy Efficiency Ratio (EER) (T1) - BTUH/W
Rated Cooling Capacity (T3) - BTUH
Rated Power Input (T3) - KW
Rated Current (T3) - AMPS
Energy Efficiency Ratio (EER) (T3) - BTUH/W
Refrigerant Used
Refrigerant charge (lb-oz)
System 1
System 2
AHRI HEATING PERFORMANCE
Heating model
Heat input (K Btu)
Heat output (K Btu)
AFUE%
Steady state efficiency (%)
No. burners
No. stages
Temperature Rise Range (ºF)
Gas Limit Setting (ºF)
Gas piping connection (in.)
DIMENSIONS (inches)
Length
Width
Height
OPERATING WT. (lbs.)
COMPRESSORS
Type
Quantity
Unit Capacity Steps (%)
CONDENSER COIL DATA
Face area (Sq. Ft.)
Rows
Fins per inch
Tube diameter (in.)
Circuitry Type
EVAPORATOR COIL DATA
Face area (Sq. Ft.)
Rows
Fins per inch
Tube diameter
Circuitry Type
Refrigerant control
18
Models
ZF180
15
YORK
Made in USA
380-415 Volts
50Hz
6000
204831
17.92
11.43
155436
20.92
36.6
7.43
R410A
22-8
21-8
N30
N40
300
400
240
320
-
-
80
80
6
8
2
2
20-50
35-65
195
195
1
1
125-1/4
92
48-5/8
1680
Scroll
2
50 / 100
36.0
3
13.5
3/8
Standard
15.5
4
14
3/8
Intertwined
TXV
Johnson Controls Unitary Products