Alarm threshold
Select setpoint for alarm 2
-999999..+999999 [Digit
72
Deviation threshold
Select deviation value from alarm 2 setpoint for the band alarm
0..+999999 [Digit
73
Hysteresis
Alarm 2 hysteresis
-10000..+10000 [Digit
74
Reset type
Alarm 2 contact reset type
Automatic
Manual
Manual stored
75
Error contact
State of contact for alarm 2 output in case of error
Open (Default)
Closed
77
Actuation delay
Alarm 2 delay. -3600..+3600 s. Default: 0
Negative: delay in alarm exit phase.
Positive: delay in alarm entry phase.
78
Lower limit
Lower limit for alarm 2 setpoint
-999999..+999999 [Digit
46 -
DP400S - User manual
], Default: 0.0.
2
], Default: 0.0.
2
], Default: 0.0.
2
(Default)
Manual reset by keyboard
Keeps relay status also after an eventual power failure
]. Default: 0.
2