Section 5 Connecting; Required Tools; Connecting Wires; Connecting Protective Grounding - ABB 620 series ANSI Installation Manual

Hide thumbs Also See for 620 series ANSI:
Table of Contents

Advertisement

1MAC457436-IB B
Section 5
5.1
5.2
5.3
620 series ANSI
Installation Manual
Connecting

Required tools

Only use a screwdriver and insert bits for Phillips (PH 2) cross-recessed head screws when
handling CT/VT terminals of screw-compression type.

Connecting wires

All connections are made on the rear of the case. No soldering is needed.
Connect each signal connector terminal with one 14 or 16 Gauge wire. Use 12 or 14
Gauge wire for CB trip circuit.
Connect each ring-lug terminal for signal connector X120 with one of maximum 14
or 16 Gauge wire.
Connect each ring-lug terminal for CTs/VTs with one 12 Gauge wire.
See the application manual for product-specific connection diagrams.

Connecting protective grounding

The ground lead must be at least a 10 Gauge wire. If the length of the
ground lead is long, the cross section of the wire must be increased.
Use fine copper wire as the ground lead.
To connect a separate ground protection lead:
Section 5
Connecting
37