Semi-Flush Mounting The Ied - ABB 620 series ANSI Installation Manual

Hide thumbs Also See for 620 series ANSI:
Table of Contents

Advertisement

1MAC457436-IB B
4.3.3
620 series ANSI
Installation Manual

Semi-flush mounting the IED

A mounting kit is needed for semi-flush mounting the IED. The mounting kit includes
screws, a raising frame and gasket.
To install a semi-flush, a panel cut-out of 9.76 x 6.38 inches (248 x 162 mm) with
mounting holes and 4.06 inches (103 mm) depth behind the panel is required.
1.
Mount the raising frame into the panel cut-out with four M5 screws.
B
D
C
GUID-0501C098-6BF8-4A0C-B448-B2CA8848C3FC V1 EN
Figure 11:
Mounting the raising frame
A 10.35 inches (263 ±0.5 mm)
B ∅ 0.24 inches (6 mm)
C 5.24 inches (133 ±0.5 mm)
D 6.38 inches (162 ±1 mm)
E 9.76 inches (248 ±1 mm)
2.
Loosen the four M5 fixing screws in the case to fit the case to the raising frame.
3.
Remove the protective film temporarily from the top side of the case.
4.
Mount the case to the raising frame.
A
E
1 Panel
2 Raising frame
3 M5 screw
Section 4
Mounting
1
2
3
23