CONFIGURATION
5

Configuration of the PROFIBUS

WARNING
!
Disconnect the inverter supply when installing the PROFIBUS Module.
NOTE
Before the inverter (with PROFIBUS module connected) is switched on, either a
Basic Operator Panel (BOP) or 'Advanced Operator Panel' (AOP) should be
inserted into the MICROMASTER 411 communications socket.
5.1

PROFIBUS address

A minimum requirement for configuring the PROFIBUS module is to establish the
PROFIBUS address setting within the network.
There are two methods of setting the PROFIBUS address; these are as follows:
Ø via jumpers on the module interface board
Ø via parameter P0918.
Figure 5-1
The PROFIBUS address can be set from 1 to 125, as shown in Table 5-1.
Table 5-1
Jumper number:
Add to address:
Example 1 – Address: 3 = 1 + 2
Example 2 – Address: 88 = 8 + 16 + 64
42
Jumpers and Termination switch
PROFIBUS Jumper Settings
PROFIBUS Communication Module
1
2
3
4
+1
+2
+4
+8
+16 +32 +64
on
on
off
off
off
off
off
off
on
on
Operating instructions
6SE6400-5AV00-0BP0
Issue 03/02
5
6
7
off
off
off
on