Functions of the XRC
The primary functions of the XRC
It performs the following with minimum effort, maximum speed and greater accuracy.
Capabilities
–
Monitoring the operational limits to insure detection and reporting of malfunctions or abnormal site conditions
–
Remote communications
–
Real-time measurement and control
–
Acceptance and storage of system parameters from PCCU32 7.05.5 or greater
–
Storage of data records
–
Storage of operational events
–
Extendable I/O count to support most customer applications
–
Multiple enclosure sizes provided to fit specific I/O requirements
–
Custom IEC 61131 applications to fit specific customer requirements
Applications
–
AGA3 orifice meter run (an external transducer required)
–
ISO 5167 orifice meter run (an external transducer required)
–
V-cone meter run (an external transducer required)
–
AGA7 rotary/turbine meter run
–
Wedge meter, liquid and gas (an external transducer required)
–
CO2, NIST 14 (an external transducer required)
–
Real-time data logger (trending)
–
Valve control (feedback controller)
Display
Description
Yesterday's Percent DP Low Limit
YEST DP LO
NN PERCENT
Percent time below DP Low Set Point
Yesterday's Percent DP High Limit
YEST DP HI
NN PERCENT
Percent time below DP High Set Point
FLOWRATE
Current Flow Rate
NNNNNN.N SCF/HR
Programmable SCF, MCF, MMCF
ACCUM VOL
Total Accumulated Volume
NNNNNN.NN MCF
Programmable SCF, MCF, MMCF
BATTERY
Battery Voltage
NN.N VOLTS
Volts
DIFF PRESS
Differential Pressure
NNN.N IN. H2O
Inches H2O
PRESSURE
Static Pressure Absolute
NNN.N PSIA
PSIA
FLOW TEMP
Flowing Temperature
NN.N DEG. F
°F
Yesterday's Volume
YEST VOL
NNNN.N MCF
Programmable SCFM, MCF, MMCF
PERIOD VOL
Previous Period Volume
NNNN.N SCF
Last volume calc. period volume
CHARGER
Charger Voltage
NN.N VOLTS
Volts
ORIFICE DIA.
Orifice Diameter
NNNN.NNNN INCHES
Inches
G4
G4
reflect a design that is practical and efficient. The XRC
14
G4