Troubleshooting
Check control fuses
ALWAYS check ECO control fuses before replacing ECO
control or any major components (blower, etc.). If one
of these fuses is blown, it can prevent ECO control or
other components from operating.
1. Turn OFF power to boiler at external line switch. Then remove
the jacket door.
2. Locate fuses using Figure 103.
3. Remove and inspect the two fuses (items 1 and 2, Figure 103).
4. If necessary, replace one or both of the fuses:
a. Low voltage circuit fuse is 3-amp fast-blow
(Littelfuse 0287003).
b. Line voltage circuit fuse is 12-amp fast-blow
(Littelfuse 0314012MXP).
Do not jumper either fuse or replace with any fuse except
as specified. Failure to comply could result in severe
personal injury, death or substantial property damage.
Checking temperature sensors
1. The boiler temperature sensors (flue, outdoor, return water and
supply water) are all resistance-type devices. Figure 102 shows
the correct value for the sensor at various temperatures. For dual
sensors, the temperature difference between the sensors must be
no more than 10°F.
2. Use the resistance values at 32°F, 60°F, 70°F and 212°F to measure
the sensor resistance at known temperatures (ice point, room
temperature and sea level boiling point). For ice point and boiling
point, insert the sensor in water at that temperature. Use an
ohmmeter to read resistance value.
3. To check whether the ECO control is correctly sensing temperature,
you can use a resistance decade box. Connect the decade box
temporarily in place of a sensor and read the corresponding
temperature on the ECO control display. The temperature should
be close to the value corresponding to the input resistance.
Figure 102
Sensor resistance values
Temp
Temp
Sensor ohms
(°F)
(°F)
Min
Max
32
34265
37871
90
40
100
27834
30764
50
21630
23907
110
60
16944
18727
120
70
13372
14780
130
80
10629
11747
140
96
2
-
G
AS
FIRED WATER BOILER
(continued)
Temp
Sensor ohms
Sensor ohms
(°F)
Min
Max
Min
8504
9399
150
2517
160
6847
7568
2091
5545
6129
170
1744
4517
4992
180
1461
3698
4088
190
1229
3043
3364
200
1038
— Boiler Manual
Figure 103
Control fuses
Line Voltage
2
1
Low
Voltage
Max
2782
2311
1928
1615
1359
1147
Part number 550-142-190/1218