Ratings — Multiple ECO Series 2 boilers
Figure 133
Ratings and engineering data — multiple ECO Series 2 boilers
Boilers in
Total
system
Input
ECO
Model
Input,
MBH
70
110 155
-
2
140
2
220
2
310
3
210
3
330
3
465
4
280
4
440
4
620
5
350
5
550
5
775
6
420
6
660
6
930
7
490
7
770
7
1085
8
560
8
880
8
1240
Boiler
Model
Shipping
Operating
weight
weight
Pounds
Pounds
per boiler
per boiler
ECO
Note 4
112
105
70
109
94
110
125
120
155
128
2
-
G
AS
FIRED WATER BOILER
Output /
Boiler
Net water
Heating
H.P.
ratings
capacity
Output,
-
MBH
MBH
Note 1
-
Note 2
130
3.9
114
202
6.0
176
286
8.5
248
195
5.8
171
303
9.1
264
429
12.8
372
260
7.8
228
404
12.1
352
572
17.1
496
325
9.7
285
505
15.1
440
715
21.4
620
390
11.7
342
606
18.1
528
858
25.6
744
455
13.6
399
707
21.1
616
1001
29.9
868
520
15.5
456
808
24.1
704
1144
34.2
992
:DWHU ÀRZ
Vent/air pipe
Water
rate
content
per boiler
(Provide a
separate
vent for each
GPM
GPM
Gallons
@ 20°F
@ 40°F
per boiler
rise
rise
2.54
6.5
3.3
2" or 3"
2.54
10.0
5.0
3.22
14.3
7.2
— Boiler Manual
Manifolded
combustion
air duct
size
1
Square
inches
Figure 60, page 54
70
2
110
155
105
165
3
233
140
220
4
310
175
275
388
210
330
465
245
385
5
543
280
440
620
Electrical
size:
service
required
Amps
per boiler
boiler)
Note 5
Note 3
15.0
3"
15.0
3"
15.0
Notes
Based on standard test procedures outlined by
DOE for individual boilers.
Net AHRI ratings are based on piping and
pickup allowance of 1.15.
Consult Weil-McLain Technical Services for
other allowances.
Total amp requirement includes up to three
circulators, not exceeding 2.2 amps per
circulator.
Operating weight is the total weight of the
boiler, including water.
ECO 70 vent/air pipes can be either 2" or 3"
pipe.
ECO 110 and 155 vent/air pipes must be 3".
All of the boilers will automatically de-rate
as vent/air pipe length increases, due to
the pressure loss through the piping. See
Figure 131, page 126 for details.
All ECO installations require a separate
vent pipe and termination for each boiler.
Vent piping cannot be manifolded
and terminate vents as described in vent/air
installation instructions in this manual.
Combustion air piping can be individually
piped or manifolded. See Figure 60, page 54,
for manifolded air piping.
Part number 550-142-190/1218