SystemAir AquaScop HT V2 Installation And Maintenance Manual

SystemAir AquaScop HT V2 Installation And Maintenance Manual

Air-water heat pump
Table of Contents

Advertisement

Quick Links

Installation and maintenance manual
Aqu@ Scop HT V2
12-6 / 18-9
Air-water Heat Pump
12.0 â 17.9kW

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the AquaScop HT V2 and is the answer not in the manual?

Questions and answers

Summary of Contents for SystemAir AquaScop HT V2

  • Page 1 Installation and maintenance manual Aqu@ Scop HT V2 12-6 / 18-9 Air-water Heat Pump 12.0 â 17.9kW...
  • Page 3 INSTALLATION INSTRUCTION English NOTICE D’INSTALLATION Français INSTALLATIONSHANDBUCH Deutsch ISTRUZIONI INSTALLAZIONE Italiano INSTRUCCIONES DE INSTALACIÓN Español...
  • Page 4: Table Of Contents

    2 Aqu@Scop HT V2 CONTENTS 1. GENERAL RECOMMENDATIONS ................................ 3 1.1. SAFETY DIRECTIONS ............................................3 1.2. WARNING ................................................. 3 1.3. EQUIPEMENT SAFETY DATA ........................................... 4 2. INSPECTION AND STORAGE ................................5 3. WARRANTY ...................................... 5 4. CONTENTS OF PACKAGE ................................... 5 5.
  • Page 5: General Recommendations

    Aqu@Scop HT V2 POWER SUPPLY MUST SWITCHED OFF BEFORE STARTING WORK IN THE ELECTRIC CONTROL BOX 1. GENERAL RECOMMENDATIONS Please read the following safety precautions very carefully before installing the unit. 1.1. SAFETY DIRECTIONS Follow the safety rules in forces when you are working on your appliance. The installation, commissioning and maintenance of these units should be performed by qualified personnel having a good knowledge of standards and local regulations, as well as experience of this type of equipment.
  • Page 6: Equipement Safety Data

    4 Aqu@Scop HT V2 1.3. EQUIPEMENT SAFETY DATA Safety Data R407C Toxicity Liquid splashes or sprays may cause freeze burns. Unlikely to be hazardous by skin absorption. However, R407C may be slightly irritant and, if liquid, it has a strong degreasing effect. Flush contaminated skin In contact with skin areas with running water.
  • Page 7: Inspection And Storage

    Aqu@Scop HT V2 2. INSPECTION AND STORAGE At the time of receiving the equipment carefully cross check all the elements against the shipping documents in order to ensure that all the crates and boxes have been received. Inspect all the units for any visible or hidden damage.
  • Page 8: Accessories

    6 Aqu@Scop HT V2 6. ACCESSORIES Set of stop cocks with pressure tap ² Set of 2 flexible pipes (length 1m) ² Hydraulic connection kit ² Sludge pot (decanting filter) ² Domestic hot water tank (300l) ² Domestic hot water plate exchanger kits for: ²...
  • Page 9: Net Weight

    Aqu@Scop HT V2 8.1. NET WEIGHT 12-6 14-7 18-9 9. TECHNICAL SPECIFICATIONS 9.1. PHYSICAL CHARACTERISTICS 12-6 14-7 18-9 REFRIGERANT Type R407C Factory charge SEE NAME PLATE HYDRAULIC LINKS Inlet water 1" Female / Rotating nut Outlet water 1" Female / Rotating nut WATER FLOW Nominal 1030 / 1230...
  • Page 10: Operating Limits

    8 Aqu@Scop HT V2 9.4. OPERATING LIMITS Aqu@ Scop HT appliances are equipped with a 2-stage output system with a ratio of 1:2. When heating needs are low and when the required outlet water temperature is below 55° C, only the first stage is used at reduced capacity until the temperature balance point is reached.
  • Page 11: Thermodynamic Domestic Hot Water Production

    Aqu@Scop HT V2 9.5. THERMODYNAMIC DOMESTIC HOT WATER PRODUCTION 9.5.1. PERFORMANCE 12-6 Configuration C2 Compressor C1+C2 Compressor Outdoor temp. °C PAC max. outlet temp. °C Average capacity 10.6 DHW temperature °C Time [min] Initial temperature: 15°C Time [min] Initial temperature: 35°C 14-7 Configuration C2 Compressor...
  • Page 12: Refrigeration And Hydraulic Diagram

    10 Aqu@Scop HT V2 10. REFRIGERATION AND HYDRAULIC DIAGRAM SEE APPENDIX 11. INSTALLATION The unit is not designed to withstand weights or stresses from adjacent equipment, pipe work or constructions. Any foreign weight or stress on the unit structure could lead to a malfunction or a collapse with dangerous consequences for personnel and property.
  • Page 13: Clearance

    Aqu@Scop HT V2 11.2. CLEARANCE When choosing the location for the appliance, take care to leave sufficient free clearance on all sides to ensure easy access for maintenance work. The minimum free clearance dimensions indicated must be observed to ensure both proper system operation and allow access for maintenance and cleaning. REF.
  • Page 14: Hydraulic Links

    12 Aqu@Scop HT V2 12. HYDRAULIC LINKS When choosing and installing water pipes, you must consult and observe all current local standards, regulations and instructions. 12.1. GENERAL RECOMMENDATIONS You must design the pipe network with the minimum number of bends and keep the number of changes in height to the strict minimum.
  • Page 15: Standard Circuits

    Aqu@Scop HT V2 12.2. STANDARD CIRCUITS 12.2.1. AQU@ SCOP HT ONLY Layout 1: Application without room by room regulation This layout is recommended when the Aqu@ Scop HT water flow is continuous and close to the nominal value (no thermostatic valves). The buffer tank (2) provides extra circulating water volume to maintain the minimum volume.
  • Page 16 14 Aqu@Scop HT V2 Layout 2: Application with room by room regulation This layout is recommended for heating installations with wide operating water flow variations (radiator thermostatic valves present in the system). We strongly recommend including the buffer tank (2) as it guarantees that the heating loop capacity is higher than the minimum volume when the maximum number of thermostatic valves are closed.
  • Page 17 Aqu@Scop HT V2 Layout 3: Application with room by room regulation This layout is also recommended for heating installations with wide operating water flow variations (radiator thermostatic valves present in the system). Minimum system volume is guaranteed by a mixing tank (10). Take care when calculating the volume of water in the installation and only take account of 50% of the mixing tank's volume.
  • Page 18 16 Aqu@Scop HT V2 Layout 4: Domestic Hot Water (DHW) production by way of the plate exchanger kit for fitment on the existing DHW tank Example for a wall-mounted tank (DHW outflow via the bottom) A different kit is required for a floor-mounted tank (DHW outflow via the top). Please refer to the corresponding documentation.
  • Page 19 Aqu@Scop HT V2 12.2.2. AQU@ SCOP HT AS A BOILER SUBSTITUTE We recommend the fitting of a zone valve to avoid heat losses via the boiler when the Aqu@ Scop HT is working on its own. All system devices should be of a suitable size to limit pressure losses. Water flow within the heating circuit is normally driven by the circulation pump already present in the installation (recommended solution) or by the Aqu@ Scop HT's circulation pump.
  • Page 20 18 Aqu@Scop HT V2 12.2.3. AQU@ SCOP HT – DUAL ZONE INSTALLATION (UNDER-FLOOR HEATING + RADIATORS) The Aqu@ Scop HT manages a radiator zone (high temperature, zone 2) and an under-floor heating zone (low temperature, zone 1) by way of an under-floor temperature outlet probe, a modulating 3-way valve (230V 3 phase motor) and a water circulation pump for each zone.
  • Page 21: Water Quality

    Aqu@Scop HT V2 12.3. WATER QUALITY The water must be analyzed; the hydraulic network system installed must include all elements necessary for water treatment: filters, additives, intermediate exchangers, drain valves, vents, check valves, etc., according to the results of the analysis. The Aqu@ Scop HTmust not run on a network with open loops, likely to cause incidents related to oxygenation, or with non treated table water.
  • Page 22: Connection To The Central Heating Loop

    20 Aqu@Scop HT V2 12.4. CONNECTION TO THE CENTRAL HEATING LOOP You must check water tightness and the cleanliness of the installation before connecting the Aqu@ Scop HT . For the Aqu@ Scop HT 's WATER INLET and OUTLET connections, you must install manual stop cocks with the same diameter as the main pipe work.
  • Page 23: Filling The System With Water

    Aqu@Scop HT V2 12.6. FILLING THE SYSTEM WITH WATER Once the installation is complete and after having clean and rinsed out the circuit network, you must fill the water circuit in accordance with current professional standards until you obtain the service pressure which will be: 0.5 bar <...
  • Page 24: Wiring Diagram And Legend

    22 Aqu@Scop HT V2 13. WIRING DIAGRAM AND LEGEND 13.1. WIRING DIAGRAM SEE APPENDIX 13.2. LEGEND N 802 SE 4213 Aqu@ Scop HT 12-6 Power 1-Phase 230V +/-10% 50Hz SE 4214 Aqu@ Scop HT 12-6 Control 1-Phase 230V +/-10% 50Hz SE 4215 Aqu@ Scop HT 14-7 Power...
  • Page 25 Aqu@Scop HT V2 KA1 : Phase sequence and cut-out control module (three phase models) µPC : Controller FT1/2 : Thermo-magnetic relays ancillary contacts for M1/2 compressors HP : Automatic reset high pressure switch EEV : Electronic pressure relief valve IHP : Intermediate high pressure switch DHP : De-icing high pressure switch RV : 4-way cycle changeover valves ISV : Injection valve...
  • Page 26 24 Aqu@Scop HT V2 13.2.3. CONTACTOR FUSE RATINGS, NOMINAL CURRENTS SETTINGS (CLASS AC3/AC1) 3N~400V +/-10% 50Hz Supply voltages 12-6 14-7 18-9 Only Aqu@ Scop HT General protection fuse rating (not supplied) aM type (1) Fuse ratings aM type T type 1.6A 1.6A 1.6A...
  • Page 27: Electrical Connections

    Aqu@Scop HT V2 14. ELECTRICAL CONNECTIONS WARNING Before carrying out any work on the equipment, make sure that the electrical power supply is disconnected and that there is no possibility unit being started inadvertently. Non-compliance with above instructions can lead to injury or death by electrocution. The electrical installation must be performed by a fully qualified electrician, and in accordance with local electrical standards and the wiring diagram corresponding to the unit model.
  • Page 28: Progressive Start-Up

    26 Aqu@Scop HT V2 14.2. PROGRESSIVE START-UP 3N~400V-50HZ The Aqu@ Scop HT 18-9 is equipped with a progressive starter (soft start) for the C1 compressor. The starter is situated in the electrical box of the outdoor unit and marked "AS1". Start slope It is important to check the following settings: Start slope...
  • Page 29: Connections

    Aqu@Scop HT V2 14.3. CONNECTIONS Remove the inspection cover to gain access to the electrical connection box. Pass the power supply cable through the cable passage provided on the appliance. Install end fittings suitable for the cable section to ensure a good contact. Make the connections as shown. 14.3.1.
  • Page 30 28 Aqu@Scop HT V2 14.3.2. AMBIENCE TERMINAL separate cables power supply (24V) communication (A-B-GND). Power supply 24V: Single pair cable: 1 mm² Communication: Shielded twisted single pair cable with screen 0.33 mm² to 0.5mm² (AWG 20/22) AMBIENCE TERMINAL CONNECTION COMMUNICATION 24V AC POWER SUPPLY 24V AC...
  • Page 31: Domestic Hot Water

    Aqu@Scop HT V2 15. DOMESTIC HOT WATER 15.1. CONNECTION TO THE CENTRAL HEATING LOOP An On-Off 3-way valve directs hot water produced by the Aqu@ Scop HT to either the heating circuit or the domestic hot water tank. Hydraulic connections must be made in accordance with the circuit layout diagrams provided.
  • Page 32: Domestic Hot Water Production Modes

    30 Aqu@Scop HT V2 15.2. DOMESTIC HOT WATER PRODUCTION MODES The Aqu@ Scop HT controller manages domestic hot water production in accordance with the following operating modes: PERMANENT COMFORT MODE ² Domestic hot water production has priority over heating except when the ambiance temperature / set temperature difference is greater than 2°...
  • Page 33: In-Line Electric Heater

    Aqu@Scop HT V2 16. IN-LINE ELECTRIC HEATER 16.1. ELECTRICAL CONNECTIONS SEE APPENDIX 16.2. OPERATING MODE Operating parameters for these modes can be set via the display on the Aqu@ Scop HT . 16.2.1. BOOST MODE The backup electric heating offers additional capacity when the demand for heating is higher than the capacity of the Aqu@ Scop HT.
  • Page 34: Boiler Relief

    32 Aqu@Scop HT V2 17. BOILER RELIEF 17.1. ELECTRICAL CONNECTIONS The boiler relief function uses the digital outputs of the in-line electric heater function to control the hot water boiler ON/OFF switch (Boiler dry contact switch) as well as a 3-way valve output (230V BRV). A switch should be wired to the ICS input to ensure operation in Back-up mode.
  • Page 35: Dual Zone

    Aqu@Scop HT V2 18. DUAL ZONE 18.1. ELECTRICAL CONNECTIONS SEE APPENDIX 18.2. ACTIVATING THE DUAL ZONE FUNCTION Power on screen Main screens P1  P4 PROG ENTER MAIN MENU Screen Reference ON/OFF-SUM/WIN HEAT CURVE L1  L4 DOMESTIC HOT WATER ES0 ...
  • Page 36: Commissioning

    34 Aqu@Scop HT V2 19. COMMISSIONING 19.1. PRE-START CHECK LIST Before commissioning the system, you must carry out a certain number of installation checks to ensure that the appliance will operate in the best possible conditions. The following list of checks is not exhaustive and only serves as a minimum reference guide.
  • Page 37: Starting The Appliance

    Aqu@Scop HT V2 20. STARTING THE APPLIANCE After checking all the electrical connections and making any rectifications as required, proceed with starting up the installation. 20.1. USER INTERFACE The terminal is a 6-button, 8-line x 22-character LCD model, which can display text in various sizes and icons.
  • Page 38 36 Aqu@Scop HT V2 20.1.3. MENUS The display comprises several menus. Some have unrestricted Power on screen access and one (the Installation menu) is password protected. All the screens include a reference in the top right hand corner to make it easier to navigate between the different menus. Main screens P1 ...
  • Page 39: Simplified Start-Up Procedure

    Aqu@Scop HT V2 20.2. SIMPLIFIED START-UP PROCEDURE 20.2.1. MAIN SCREENS On the Aqu@ Scop HT display, after having checked the coherence of the temperature probes on the main screens P1, P2 and P3, as well as effective communication with the ambience terminal, it is advisable to set the heat curve parameters before starting the Aqu@ Scop HT.
  • Page 40 38 Aqu@Scop HT V2 Outdoor temperature probe. This probe should not be installed remotely. Ambience terminal Activation/deactivation (Default setting: activated). The temperature differential parameters in relation to the set ambient temperature control the starting and stopping of the Aqu@ Scop HT in terms of ambient temperature (even though the water law is also managed by ambient temperature conditions).
  • Page 41 Aqu@Scop HT V2 20.2.3. HEAT CURVE PARAMETERS On the main menu (key ), use the arrows to highlight the "HEAT CURVE" menu. Validate this selection with the key. This moves the display to the L1 screen. Use the keys to set the following parameters: Screen L1 Altitude: Installation site altitude, in km (e.g.
  • Page 42 40 Aqu@Scop HT V2 20.2.4. VERIFICATION OF COMMUNICATION WITH THE COMMUNICATING AMBIENCE TERMINAL Screen TH1 By default, the ambience terminal is declared in the regulator. This means that an alarm will be visible on the screen of the Aqu@ Scop HT a few seconds after the power supply is switched on, if the terminal is not connected.
  • Page 43 Aqu@Scop HT V2 20.2.7. AQU@ SCOP HT ON/OFF SETTINGS In order to start, the Aqu@ Scop HT must always be ON at the level of the appliance's display. In addition, the ambience terminal must be in demand mode (when it is connected). To force the terminal to enter demand mode, change it to Comfort mode with an ambience temperature set at 30°...
  • Page 44: Operating Check List

    42 Aqu@Scop HT V2 20.3. OPERATING CHECK LIST 20.3.1. GENERAL Cheek for any unusual noises or vibration in the running components, particularly the fan drive system. 20.3.2. PHASE ROTATION PROTECTION If the phase of the power supply are not correct, the phase rotation protection device will prevent the machine from starting.
  • Page 45: Final Tasks

    Aqu@Scop HT V2 21. FINAL TASKS Place the plugs back on the valves and check that they are properly tightened. If needed, fix the cables and the pipes on the wall with clamping collars. Operate the Aqu@ Scop HT in the presence of the user and explain all functions. 22.
  • Page 46: Maintenance

    44 Aqu@Scop HT V2 24. MAINTENANCE The user is responsible for ensuring that the unit is in perfect working order and that the technical installation and minimum annual maintenance operations have been performed by a qualified technician in accordance with the procedures described in the present manual. Some alarms can only be cancelled by switching the Aqu@ Scop HT to OFF.
  • Page 47 Aqu@Scop HT V2 24.1.5. ELECTRICAL EQUIPMENT Les interventions dans les boitiers électriques sont réalisées pars des techniciens habilités. 1. Check that the main power supply cable is not damaged or altered in such a way as to affect the insulation. 2.
  • Page 48: Alarm List Available On The Aqu@ Scop Ht Display

    46 Aqu@Scop HT V2 25. ALARM LIST AVAILABLE ON THE AQU@ SCOP HT DISPLAY Software version: 6.0 Some terms may differ depending on the software version.
  • Page 49 Aqu@Scop HT V2...
  • Page 50 48 Aqu@Scop HT V2...
  • Page 51 Aqu@Scop HT V2...
  • Page 52 50 Aqu@Scop HT V2...
  • Page 53 Aqu@Scop HT V2...
  • Page 54 52 Aqu@Scop HT V2...
  • Page 55: Faulty Diagnosis Guide

    Aqu@Scop HT V2 26. FAULTY DIAGNOSIS GUIDE Simple diagnosis advice. In the event of a breakdown, you should contact your local after sales department for confirmation and assistance. Compressor does not start Problem symptoms Probable cause Recommended action Power is present at the compressor terminal but the motor Motor burnt out Replace the compressor...
  • Page 56 54 Aqu@Scop HT V2 Excessively high discharge pressure Problem symptoms Probable cause Recommended action Major difference between Presence of incondensable matter in the system or Bleed the incondensable matter and drain off condensing and water outlet excessive refrigerant fluid charge the excess refrigerant fluid temperatures Presence of air in water circuit...
  • Page 57 APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO...
  • Page 58 APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO APPENDIX DIMENSIONS ................III BOILER RELIEF + DOMESTIC HOT WATER TANK .........XVII ELECTRIC HEATER + DOMESTIC HOT WATER TANK ......XVIII REFRIGERATION AND HYDRAULIC LINKS DIAGRAM ....IV ELECTRIC HEATER + DUAL ZONE KIT ..........XVIII WATER FLOW CALCULATION GRAPH ........
  • Page 59 APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO DIMENSIONS DIMENSIONS ABMESSUNGEN DIMENSIONI DIMENSIONES 1374 1456.60 1244 1244.5 Aqu@Scop HT V2...
  • Page 60 APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO REFRIGERATION AND HYDRAULIC LINKS DIAGRAM SCHEMA FRIGORIFIQUE ET HYDRAULIQUE KÜHL- UND HYDRAULIKDIAGRAMM SCHEMA FRIGORIFERO ED IDRAULICO ESQUEMA FRIGORÍFICO E HIDRÁULICO Large compressor Gros compresseur Kompressor Niederdruck Small compressor Petit compresseur Kompressor Hochdruck Plate heat exchangers.
  • Page 61 APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO Aqu@Scop HT V2...
  • Page 62 APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO WATER FLOW CALCULATION GRAPH ABAQUE DE CALCUL DE DEBIT D'EAU BERECHNUNGSKURVE DER WASSERDURCHFLUSSMENGE ABACO DI CALCOLO DELLA PORTATA DELL'ACQUA ÁBACO DE CÁLCULO DE CAUDAL DE AGUA Aqu@ Scop HT 12-6 Circulator operating range Plage de fonctionnement du circulateur Betriebsbereich des Umlaufpumpe Zona di funzionamento del circulador...
  • Page 63 APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO WIRING DIAGRAM SCHEMAS ELECTRIQUES STROMLAUFPLANS SCHEMA ELETRICO ESQUEMA ELECTRICO TAKE CARE! These wiring diagrams are correct at the time of publication. Manufacturing changes can lead to modifications. Always refer to the diagram supplied with the product. ATTENTION Ces schémas sont corrects au moment de la publication.
  • Page 64 APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO AQU@ SCOP HT 12-6 230V +/-10% 50HZ VIII Aqu@Scop HT V2...
  • Page 65 APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO Aqu@Scop HT V2...
  • Page 66 APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO AQU@ SCOP HT 14-7 230V +/-10% 50HZ X Aqu@Scop HT V2...
  • Page 67 APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO Aqu@Scop HT V2...
  • Page 68 APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO AQU@ SCOP HT 12-6 / 14-7 3N~400V +/-10% 50HZ XII Aqu@Scop HT V2...
  • Page 69 APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO Aqu@Scop HT V2 XIII...
  • Page 70 APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO AQU@ SCOP HT 18-9 3N~400V +/-10% 50HZ XIV Aqu@Scop HT V2...
  • Page 71 APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO Aqu@Scop HT V2...
  • Page 72 APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO DOMESTIC HOT WATER PLATE EXCHANGEUR KIT KIT EAU CHAUDE SANITAIRE AVEC ECHANGEUR A PLAQUES BAUSÄTZE SANITÄRES WARMWASSER MIT PLATTENAUSCHER KIT ACQUA CALDA SANITARIA CON SCAMBIATORE A PIASTRE KIT AGUA CALIENTE SANITARIA CON CAMBIADOR DE PLACAS SE 4287 KIT ECS AQU@SCOP HT V2...
  • Page 73 APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO BOILER RELIEF + DUAL ZONE KIT RELEVE DE CHAUDIERE + KIT DOUBLE ZONE HEIZKESSELEINBINDUNG + DOPPELZONEN-VERWALTUNGSBAUSATZ CAMBIO DI CALDAIA + KIT RADDOPPIA ZONA RELEVO DE CALDERA + KIT DOBLA ZONA SE 4289 RELEVE DE CHAUDIERE + DOUBLE ZONE AQU@SCOP HT V2...
  • Page 74 APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO ELECTRIC HEATER + DOMESTIC HOT WATER TANK RECHAUFFEUR ELECTRIQUE + BALLON D'EAU CHAUDE SANITAIRE ELEKTRISCHE HEIZUNG + BRAUCHWASSERVERSORGUNG RISCALDATORE ELETTRICO + PALLA DI ACQUA CALDA SANITARIA CALENTADOR ELECTRICO + ACUMULADOR DE AGUA CALIENTE SANITARIA SE 4291 KIT RECHAUFFEUR + BALLON ECS...
  • Page 75 APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO DOMESTIC HOT WATER TANK + DUAL ZONE KIT BALLON D'EAU CHAUDE SANITAIRE + DOUBLE ZONE BRAUCHWASSERVERSORGUNG + DOPPELZONEN-VERWALTUNGSBAUSATZ PALLA DI ACQUA CALDA SANITARIA + KIT RADDOPPIA ZONA ACUMULADOR DE AGUA CALIENTE SANITARIA + KIT DOBLA ZONA SE 4293 KIT BALLON ECS + DOUBLE ZONE...
  • Page 76 APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO DOMESTIC HOT WATER TANK BALLON D'EAU CHAUDE SANITAIRE BRAUCHWASSERVERSORGUNG PALLA DI ACQUA CALDA SANITARIA ACUMULADOR DE AGUA CALIENTE SANITARIA AQU@SCOP HT µPC µPC REGULATEUR DE L'AQU@SCOP HT DHW WT BALLON D'EAU CHAUDE SANITAIRE µPC AQU@SCOP HT CONTROLLER DHW WT DOMESTIC HOT WATER TANK...
  • Page 77 APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO PERFORMANCES PERFORMANCES LEISTUNGSTABELLE POTENZA POTENCIA AQU@ SCOP HT 12-6 A-15 Outdoor temperature T entré air T Lufteingang Temperatura entrata di aria Temperatura entrada por aire Outlet water temperature T sortie eau T Wasserausgang Temperatura uscita di acqua Temperatura sacada de agua...
  • Page 78 APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO AQU@ SCOP HT 14-7 A-15 Outdoor temperature T entré air T Lufteingang Temperatura entrata di aria Temperatura entrada por aire Outlet water temperature T sortie eau T Wasserausgang Temperatura uscita di acqua Temperatura sacada de agua Water flow Débit d'eau...
  • Page 79 APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO Aqu@Scop HT V2 XXIII...
  • Page 80 APPENDIX / ANNEXE / ANLAGE / ALLEGATO / ANEXO XXIV Aqu@Scop HT V2...
  • Page 84 As part of our ongoing product improvement programme, our products are subject to change without prior notice. Non contractual photos. Systemair AC SAS Route de Verneuil 27570 Tillières-sur-Avre FRANCE & : +33 (0)2 32 60 61 00 6 : +33 (0)2 32 32 55 13...