About Calibration Windows and Default Calibration Values

PLUS+1 Compliant JS6000 XY-Axis Joystick Function Block
User Manual
JS6000_XY Function Block
The following graph shows the relationship between the default calibration values and the
windows in which the function block captures calibration values during autocalibration.
The JS6000_XY function block's SnsrPwr is 5000 mV.
The JS6000_XY function block's default:
CalLow calibration value is 1000, or 10% (500 mV) of SnsrPwr.
CalMid calibration value is 5000, or 50% (2500 mV) of SnsrPwr.
CalHi calibration value is 9000, or 90% (4500 mV) of SnsrPwr.
The JS6000_XY function block's CalWindow (Calibration window) is 1000, or 500 mV
wide (10% of SnsrPwr).
(The Default values for CalLow, CalMid, and CalHi are set in the Memory page. The
CalWindow value is set in the JS6000_XY page.)
The 500 mV wide calibration windows center on the Default values for CalLow,
CalMid, and CalHi.
11007142 · Rev BA · September 2011