2
NX-320E Remote Power Supply
Installation Manual
Product overview
The NX-320E is a microprocessor-controlled remote power supply module for the NetworX control panels.
The module has three programmable outputs (A, B, C) and one programmable style Y bell output. You can add
up to eight power supply modules for a total of 32 outputs. You can use the A, B, and C programmable outputs
as auxiliary power, for smoke detectors and sirens. (See
has a tamper terminal that can be used to supervise the metal enclosure. Do not use more than 2500 ft. of wire
from the NX-320E to all outgoing devices.
Product contents
The NX-320E Remote Power Supply includes the following:
•
Board
•
Board guides
•
Transformer
•
Diodes (2), black wrap is for fire installation
•
Resistors (2), white wrap for fire installation
You will also need the following items that are not included with the NX-320E:
•
22 gauge 4-conductor wire (Table 1 on page 4)
•
Battery (Table 3 on page 6)
UL requirements
The NX-320E meets the Underwriters Laboratories (UL) standards, including the following:
•
UL365 Police Station Connected Burglar Alarm Units and Systems
•
UL609 Local Burglar Alarm Units and Systems
•
UL864 Control Units for Fire-protective Signaling Systems
•
UL985 Household Fire Warning Systems
•
UL1023 Household Burglar Alarm Systems
•
UL1610 Central Station Burglar Alarm Units
When the NX-320E is part of a UL commercial fire security system, this unit is compatible with the following:
•
NX-148E-CF LCD keypad
•
NX-216E zone expander
•
NX-507E relay expander
•
13-474 horn/strobe 15-75 CD (for proper strobe operation, change Location 6, Segment 1 from 16 to
13)
For UL installations, the Class II, Class III, and power-limited fire alarm circuits must be installed using FPL,
FPLP, FPLR, CLIII, CLIIIR, or CLIIIP, or substitute cable permitted by National Electrical Code ANSI/
NFPA70. If you have Class II, Class III, and power-limited fire alarm circuit conductors that extend beyond the
cable jacket, separate the wires by a 0.25 in. from all other conductors or use nonconducting tubing.
Specifications
on page 19.) Each power supply module