NX-320E Remote Power Supply
Installation Manual

Product overview

The NX-320E is a microprocessor-controlled remote power supply module for the NetworX control panels.
The module has three programmable outputs (A, B, C) and one programmable style Y bell output. You can add
up to eight power supply modules for a total of 32 outputs. You can use the A, B, and C programmable outputs
as auxiliary power, for smoke detectors and sirens. (See
has a tamper terminal that can be used to supervise the metal enclosure. Do not use more than 2500 ft. of wire
from the NX-320E to all outgoing devices.

Product contents

The NX-320E Remote Power Supply includes the following:
Board
Board guides
Transformer
Diodes (2), black wrap is for fire installation
Resistors (2), white wrap for fire installation
You will also need the following items that are not included with the NX-320E:
22 gauge 4-conductor wire (Table 1 on page 4)
Battery (Table 3 on page 6)

UL requirements

The NX-320E meets the Underwriters Laboratories (UL) standards, including the following:
UL365 Police Station Connected Burglar Alarm Units and Systems
UL609 Local Burglar Alarm Units and Systems
UL864 Control Units for Fire-protective Signaling Systems
UL985 Household Fire Warning Systems
UL1023 Household Burglar Alarm Systems
UL1610 Central Station Burglar Alarm Units
When the NX-320E is part of a UL commercial fire security system, this unit is compatible with the following:
NX-148E-CF LCD keypad
NX-216E zone expander
NX-507E relay expander
13-474 horn/strobe 15-75 CD (for proper strobe operation, change Location 6, Segment 1 from 16 to
13)
For UL installations, the Class II, Class III, and power-limited fire alarm circuits must be installed using FPL,
FPLP, FPLR, CLIII, CLIIIR, or CLIIIP, or substitute cable permitted by National Electrical Code ANSI/
NFPA70. If you have Class II, Class III, and power-limited fire alarm circuit conductors that extend beyond the
cable jacket, separate the wires by a 0.25 in. from all other conductors or use nonconducting tubing.
Specifications