Table 7- 2
Test voltages for 6EP1336-3BA00 and 6EP1337-3BA00
Type test
Production test
Field test
Remark:
Tripping current for DC measurement: 0 mA
Tripping current for AC measurement: <100 mA
SITOP modular 1ph/2ph
Operating Instructions, 06.2014, C98130-A7548-A1-3-7629
Test time
60 s
60 s
1 s
1 s
1 s
1 s
Prim ↔ sec (A)
4200 VDC
3000 VAC
2200 VDC
1500 VAC
2200 VDC
1500 VAC
Safety, approvals, EMC
Prim ↔ PE (B)
2200 VDC
1500 VAC
2200 VDC
1500 VAC
2200 VDC
1500 VAC
7.2 Test voltage
Sec ↔ PE (C)
700 VDC
500 VAC
500 VDC
350 VAC
500 VDC
350 VAC
53