6.2

Output

Output
Rated voltage value Ua rated
DC
Total tolerance, static ±
Static line regulation, approx.
Static load regulation, approx.
Residual ripple in the load
range
Peak-peak, max.
Spikes peak-peak, max.
(bandwidth, approx. 20 MHz)
Adjustment range
Product function / output
voltage can be adjusted
Output voltage setting
Remark
Output derating Ua/T
Output derating Ua/Ia
Output derating Ua/Ui
Remark
Response when switching
on/off
Starting delay, max.
Voltage rise, typ.
Voltage rise time of the output
voltage, maximum
Rated current value Ia rated
Current range
Remark
Output active power / typical
SITOP modular 1ph/2ph
Operating Instructions, 06.2014, C98130-A7548-A1-3-7629
6EP1333-3BA10
6EP1334-3BA10
(24 V/5 A)
(24 V/10 A)
Regulated, isolated DC voltage
24 V
3 %
3 %
0,1 %
0,1 %
0,1 %
0,1 %
50 mV
50 mV
200 mV
200 mV
24...28.8 V
Yes
Via potentiometer
Max. 120 W
Max. 240 W
See Figure 6-7 Output derating depending on the ambient temperature at Ia rated
(Page 42)
See Figure 6-8 Output derating depending on the output current at 60° C (Page 42)
-
-
Overshoot of Ua approx. 3%
1 s
1 s
50 ms
50 ms
500 ms
500 ms
5 A
10 A
0...5 A
0...10 A
+60°..+70° C
derating:
Approx. 2%
Ia rated/K
120 W
240 W
6EP1336-3BA00
6EP1337-3BA00
(24 V/20 A)
(24 V/40 A)
3 %
3 %
0,1 %
0,1 %
0,1 %
0,1 %
100 mV
100 mV
200 mV
200 mV
Max. 480 W
Max. 960 W
-
See Figure 6-9
Output derating
depending on the
input voltage
(Page 43)
The output voltage
must not be set
higher than 24 V for
85 to 93 VAC.
0.1 s
0.1 s
50 ms
50 ms
500 ms
500 ms
20 A
40 A
0...20 A
0...40 A
+60°..+70° C
+60°..+70° C
derating:
derating:
Approx. 2%
Approx. 2%
Ia rated/K
Ia rated/K
480 W
960 W
Technical data