Installation and Maintenance Manual
BACnet
VAV Actuator
®
Electronic Output
Start-up Procedures
IM 1040
Group: Controls
Part Number: IM 1040
Date: April 2015

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the BACnet and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Daikin BACnet

  • Page 1 Installation and Maintenance Manual IM 1040 Group: Controls Part Number: IM 1040 Date: April 2015 BACnet VAV Actuator ® Electronic Output Start-up Procedures...
  • Page 2: Table Of Contents

    Performing the automated checkout ....8 Configuring BACnet parameters ....8 IM 1040 •...
  • Page 3: Introduction

    Daikin Applied disclaims any liability resulting from any interference or for the correction thereof.
  • Page 4: Start-Up Procedures

    Setting controller address NOTICE NOTICE WinCIS version 2.1.4 or later must be used to configure Daikin For BACnet, the controller address is the same as the BACnet BACnet controllers. MAC address. NOTICE If WinCIS does not communicate (through the HMI port / RTS sensor), try a different baud rate.
  • Page 5: Enabling Actuators

    If any of the actuators still do not close completely, then SSB81U the actuators have been installed or set up incorrectly. See Floating control fail in-place the installation instructions or contact your local Daikin SSC81U representative. Floating control fail in-place SSC81.5U...
  • Page 6: Selecting Automatic Calibration Option

    TarT roCedures Enabling autozero module Setting room temperature setpoints NOTICE CAUTION If STPT DIAL is set to YES, do not set the DAY (or OCC) If an Autozero Module is used, do not enable MTR3 (valve 2). setpoints; the value of RM STPT DIAL will be used for these points.
  • Page 7: Setting Flow Coefficient

    TarT roCedures Setting flow coefficient Setting airflow setpoints 1. Set FLOW COEFF to the appropriate value found in CAUTION Table 6. This value is a starting point for the air balancer. If using electric heat in a unit without a terminal fan, do not set 2.
  • Page 8: Performing The Automated Checkout

    Checkout procedure has not been run since last controller initialization. CTLR (12 character RAD50 limit). No errors found. • Object ID – unique to BACnet network, valid values = 0 to RTS failed. 4,194,303. Room Setpoint dial dialed [if STPT DIAL (Point 14) = YES].
  • Page 10 Daikin Applied Training and Development Now that you have made an investment in modern, efficient Daikin equipment, its care should be a high priority. For training information on all Daikin HVAC products, please visit us at www.DaikinApplied.com and click on Training, or call 540-248-9646 and ask for the Training Department.