ID Address

Because there are not enough buttons/LEDs to address the full 0-
255 ID range, the ID must be entered in two stages. The three most
significant ID bits are entered first, followed by the five least
significant ID bits.
ON
A
B
C
D
OFF
ON
A
B
C
D
OFF
ON
A
B
C
D
OFF
Step 1. Press and hold A and D for 3 or more
seconds. (ON LED will blink On 75% and
Off 25%.)
Step 2. Enter three most significant ID bits in C-
D-OFF. Use Raise/Lower to increment/
decrement value.
Step 3. Press ON. (ON LED will blink On 25%
and Off 75%.)
Step 4. Enter five least significant ID bits in A-B-
C-D-OFF. Use Raise/Lower to
increment/decrement value.
Step 5. Press ON to save and exit.
ID Values:
C = 128 (most significant ID)
D = 64 (most significant ID)
OFF = 32 (most significant ID)
A = 16 (least significant ID)
B = 8 (least significant ID)
C = 4 (least significant ID)
D = 2 (least significant ID)
OFF = 1 (least significant ID)
6-Button Remote Station User's Guide